Included PowerAlert Software provides e-mail notification of power problems and the simultaneous automatic unattended shutdown of multiple servers

4 built-in communications ports (2-DB9, 2-USB) for remote monitoring and unattended shutdown

Slot for SNMP/web card (part#: SNMPWEBCARD) and environmental sensor (part#: ENVIROSENSE) for remote communications in large IP environments

Supports Tripp Lite's WatchDog software application to restore unresponsive programs by automatically restarting them and rebooting completely locked computers by automatically switching UPS power off and back on again

Communication ports support on battery, low battery, power restored, AC line voltage, DC battery voltage, load percentage, battery charge current, battery capacity, internal UPS temperature and line frequency status messaging. Interface supports timed inverter shutoff after unattended shutdown, activate self-test and 10 second reboot of connected equipment

3 individual customized load management receptacles can be individually powered off and back on again via software interface to reboot remote equipment or perform "load shedding" of less critical loads to extend battery runtime for the most critical equipment

Built-in Emergency Power Off (EPO) interface supports emergency shutoff in large facilities

Hot-swappable/user replaceable batteries allow on-site battery replacement through the front panel without powering off connected equipment or removing the UPS from the rack

UPS battery set ships fully assembled and ready for use, no time consuming, connection of individual internal batteries by user is necessary

UL (USA), cUL (Canada), NOM (Mexico), FCC Class A

$250,000 Ultimate Lifetime Insurance. No warranty cards required for coverage! 2 year manufacturer's product warranty

Specifications

SYSTEM OVERVIEW

Voltage compatibility

120V AC

 

 

Frequency

60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

3000

 

 

Output watts

2250

 

 

Output nominal

120V AC

voltage

 

 

 

Output voltage

LINE MODE: Sine wave line voltage 120V (-18% / +8%), BATTERY MODE: PWM sine wave output 120V +/-5%

regulation

 

 

 

Output frequency

LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz

regulation

 

 

 

Outlet quantity / type

7 NEMA 5-15R, 2 NEMA 5-20R and 1 NEMA L5-30R

 

 

Customized load

"3 individually controllable outlets support load shedding and remote reboot on demand of locked network devices.

management

Controllable via PowerAlert software to switch off optional loads, like monitors, to increase available runtime for servers

receptacles

and other critical devices. "

 

 

Overload protection

Via 30A input breaker and 2 15A output breakers

 

 

INPUT

 

Maximum input amps

24 amps

 

 

Input connection type

NEMA L5-30P

 

 

Input cord length

8 ft.

 

 

Recommended

120V 30A

Electrical Service

 

 

 

BATTERY

 

Full load runtime

4 minutes

 

 

Half load runtime

14 minutes

 

 

Expandable battery

Runtime is expandable with BP48V24-2U (limit 1) or BP48V60RT3U (multi-pack compatible) external battery packs

runtime

 

 

 

DC system voltage

48 VDC

Page 2
Image 2
Tripp Lite SMART3000VS warranty Specifications, System Overview, Output, Input, Battery