Typical battery lifespan
Battery recharge rate
Replacement Battery Cartridge
RBC54
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Direct pass through
Brownout correction
Severe brownout correction
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated
Input voltages between 128 and 147VAC are reduced by 12%
Input voltages between 105 and 127VAC are passed on to connected equipment unchanged
Input voltages between 95 and 104VAC are boosted by 12%
Input voltages between 79 and 94VAC are boosted by 24%
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information
3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) and low battery (continuous tone)
Yes, includes 2 front panel mounted
SURGE / NOISE SUPPRESSION
AC surge | 480 joules |
suppression |
|
|
|
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 66 |
|
|
Shipping weight (kg) | 30 |
|
|
Shipping | 16 x 14.75 x 19.75 |
Dimensions (HWD/in) |
|
|
|
Shipping | 40.6 x 37.5 x 50.2 |
Dimensions |
|
(HWD/cm) |
|
|
|
Unit weight (lbs) | 59 |
|
|
Unit weight (kg) | 26.8 |
|
|
Unit Dimensions | 14.25 x 9.25 x 12 |
(HWD/in) |
|
|
|
Unit Dimensions | 36.2 x 23.5 x 30.5 |
(HWD/cm) |
|
|
|
Material of | Polycarbonate |
construction |
|
|
|
Form factors | Tower |
supported |
|
|
|
Cooling method | |
|
|
Battery Access | Battery access door enables user battery replacement, |
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|