Voltage regulation description

Overvoltage correction

Direct pass through

Brownout correction

Severe brownout correction

Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using battery power, during brownouts to 75V and overvoltages to 147V

Input voltages between 128 and 147V AC are reduced by 12%

Input voltages between 108 and 127V AC are passed on to connected equipment unchanged

Input voltages between 93 and 107V AC are boosted by 14%

Input voltages between 75 and 92V AC are boosted by 30%

LEDS ALARMS & SWITCHES

Front panel LEDs

Alarms

Switches

Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information

Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.

Includes 2 front panel switches—one main on/off power switch and one dual function "alarm cancel" / "self test" button

SURGE / NOISE SUPPRESSION

AC surge

1800 joules

suppression

 

 

 

AC suppression

Instantaneous

response time

 

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight (lbs)

24

 

 

Shipping weight (kg)

10.9

 

 

Shipping Dimensions

15.5 x 11 x 11.25

(HWD/in)

 

 

 

Shipping Dimensions

39.4 x 28 x 28.6

(HWD/cm)

 

 

 

Unit weight (lbs)

22

 

 

Unit weight (kg)

10.0

 

 

Unit Dimensions

11.75 x 7.25 x 7.5

(HWD/in)

 

 

 

Unit Dimensions

29.8 x 18.4 x 19.1

(HWD/cm)

 

 

 

Material of

PVC

construction

 

 

 

Form factors

Tower

supported

 

 

 

Cooling method

Convection

 

 

Battery Access

Battery access door allows user replacement of UPS batteries

 

 

ENVIRONMENTAL

 

Relative Humidity

0 to 95%, non-condensing

 

 

Storage Temperature

+5 to +122 degrees Fahrenheit

 

 

Operating

+32 to +104 degrees Fahrenheit

Temperature

 

 

 

COMMUNICATIONS

 

Network monitoring

Built-in USB port supports on battery, low battery, power restored, AC line voltage, DC battery voltage, load

port

percentage, battery charge current, battery capacity, internal UPS temperature and line frequency status messaging.

 

Interface supports timed inv

 

 