compatible)
Full line isolation prevents shock potential and operational problems in sensitive electronic equipment
Resistant to electrostatic discharge
Supports loads up to 1000VA/750W
27.5 min.
6 protected outlets;
USB and DB9 communication ports
PowerAlert unattended shutdown software and complete cabling included
Complete surge protection, line isolation and EMI/RFI noise filtering
5 diagnostic LEDs indicate AC present, on battery, voltage correction, overload & battery low/replace
Battery replacement door and back panel grounding lug
Specifications
SYSTEM OVERVIEW
Voltage compatibility | 230V AC |
|
|
Frequency | 50/60 Hz |
compatibility |
|
|
|
OUTPUT |
|
Output VA | 1000 |
|
|
Output watts | 750 |
|
|
Output nominal | 230V AC |
voltage |
|
|
|
Output voltage | LINE MODE: Sine wave line voltage 230V |
regulation |
|
|
|
Output frequency | LINE MODE: Passes line frequency of 50/60Hz |
regulation |
|
|
|
Outlet quantity / type | 6 IEC320 C13 |
|
|
INPUT |
|
Maximum input amps | 5A / 1150 watts |
|
|
Input connection type | IEC320 C14 inlet |
|
|
Input cord length | 6 inch dongle, 16 gauge |
|
|
Recommended | 10A 230V |
Electrical Service |
|
|
|
BATTERY |
|
Full load runtime | 11 min. (1000VA) |
|
|
Half load runtime | 27.5 min. (500VA) |
|
|
Expandable battery | Supports extended runtime with optional |
runtime | compatible) |
|
|
DC system voltage | 36V DC |
|
|
Typical battery | |
lifespan |
|
|
|
Battery recharge rate | |
|
|
VOLTAGE REGULATION |
|
Voltage regulation | Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to |
description | maintain usable, computer grade output without consuming battery power over an input voltage range of 155 to 274V |
| AC. |
|
|