Rack Height
Secondary form factor
UPS / Power Module weight (lbs)
UPS / Power Module weight (kg)
UPS Shipping dimensions (height x width x depth / inches)
3U
Tower (requires
143
64.9
11.3 x 23 x 31.5
UPS Shipping dimensions (height x width x depth / cm)
Shipping weight (lbs)
Shipping weight (kg)
Cooling method
UPS housing material
ENVIRONMENTAL
28.6 x 58.4 x 80
182
82.6
Fans
Steel
Operating Temperature Range
Storage Temperature Range
Relative Humidity
AC mode BTU / hr. (full load)
AC mode efficiency rating (100% load)
COMMUNICATIONS
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit /
0 to 95%,
271
98%
Communications interface
Network monitoring port description
PowerAlert software
Communications cable
WatchDog compatibility
LINE / BATTERY TRANSFER
USB; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface
Supports detailed monitoring of UPS and site power conditions
Included
USB and DB9 cabling included
Supports Watchdog application, OS and
Transfer time
Low voltage transfer to battery power (setpoint)
High voltage transfer to battery power (setpoint)
170
282
SPECIAL FEATURES
Grounding lug
Cold Start (startup in battery mode during a power failure)
Back panel grounding lug