Features

Specifications Two sets of 4-post rackmount rails (one for each of the 3U components)

SYSTEM OVERVIEW One set of tower stands for upright tower configuration

OUTPUT PowerAlert Software, complete cabling, owner's manual with warranty information

Features

INPUT 10,000VA (10kVA) on-line, double-conversion UPS system (high-voltage input/high-voltage output)

BATTERY Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without powering off connected equipment

Manual background Installs in only 6 rack spaces (3U power module/3U battery pack) with a maximum installed depth of 32.5 in.

Manual background Offers 4 min. runtime at full load (10,000VA/8000W) and 10 min. at half load (5000VA/4000W). Runtime is expandable with any number of optional external battery packs

Manual background Full-time sine wave 200, 208, 220, 230, or 240V +/-2% output (user selectable)

Manual background Actively converts raw incoming AC power to DC, then re-converts output to completely regulated, filtered AC output

Manual background Operates continuously without using battery power during brownouts to 156V and overvoltages to 276V

Manual background Standard 3-wire 208V hardwire input connection

Manual background 4 x NEMA L6-20R and 2 x NEMA L6-30R output receptacles

Manual background Detailed LCD panel with scroll buttons provides detailed diagnostic test information on startup and during self tests, plus real-time data on input and output voltage, frequency (Hz), load percentage, battery charge level and more

Manual background Network-grade AC surge and noise suppression

Manual background Zero transfer time between AC and battery operation

Manual background Includes slot for internal SNMP/web card, plus DB9 enhanced serial monitoring port, and contact closure port for unattended shudown, remote control and monitoring of UPS system and power data

Manual background Supports detailed monitoring of equipment load levels, self-test data and mains power conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling

Manual background Emergency Power Off (EPO) interface

Manual background Front panel LEDs provide at-a-glance confirmation of line power status, battery power status, AC-to-DC & DC-to-AC conversion, bypass mode and output power status

Manual background Fault-tolerant auto-bypass mode prevents loss of output during UPS fault conditions or excessive UPS loading

Manual background 4-post rackmount and upright tower installation accessories included; 2POSTRMKITWM 2-post rackmount hardware accessories available

Manual background Field-replaceable, hot-swappable power module and external battery packs

Manual background Attractive all-black color scheme

Manual background 2-year warranty; extended warranty and service contracts available Manual background $250,000 connected equipment insurance

Specifications

SYSTEM OVERVIEW

Voltage compatibility

208V AC (200/208/220/230/240V)

 

 

Frequency

50/60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

10000

 

 

Output watts

8000

 

 

Output nominal

208V AC (200/208/220/230/240V)

voltage

 

 

 

Output voltage

Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 3% total

regulation

harmonic distortion when used with computer loads

 

 

Output frequency

Regulates line frequency to 50/60Hz +/- 0.05Hz

regulation

 

 

 

Outlet quantity / type

4 x NEMA L6-20R, 2 x NEMA L6-30R

 

 

INPUT

 

Maximum input amps

200V-46.7A / 208V- 44.9A / 220V- 42.4A / 230V-40.6A / 240V-38.9A

 

 

Input connection type

Hardwire

 

 

BATTERY

 