Full load runtime
Half load runtime
Connects to UPS via
DC system voltage
Typical battery lifespan
Battery recharge rate
4 min. (10,000VA/8000W)
10 min. (5000VA/4000W)
Included
240VDC
Less than 8 hours to 90% (included battery set only)
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Brownout correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within 2% of selected nominal
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC, regulating output within 2% of selected nominal
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 331 |
|
|
Shipping weight (kg) | 150.3 |
|
|
Shipping Dimensions | 39.75 x 31.5 x 23 |
(HWD/in) |
|
|
|
Shipping Dimensions | 101 x 80 x 58.4 |
(HWD/cm) |
|
|
|
Unit weight (lbs) | Power Module 55 lbs., Battery Pack: 136.5 lbs. |
|
|
Unit weight (kg) | Power Module 25 kg., Battery Pack: 62 kg |
|
|
Unit Dimensions | Power Module 5.14 x 17.5 x 25, Battery Pack 5.16 x 17.5 x 25 (Installed depth of power module extends to 32.5 inches |
(HWD/in) | with detachable PDU backplate installed) |
|
|
Unit Dimensions | Power Module 13.3 x 44.4 x 63.5, Battery Pack 13.4 x 40.6 x 63.5 (Installed depth of power module extends to 82.6 cm |
(HWD/cm) | with detachable PDU backplate installed) |
|
|
Material of | Steel |
construction |
|
|
|
Form factors | Rack (6U) |
supported |
|
|
|
Cooling method | Fan |
|
|
Battery Access | User replaceable, hot swappable external battery pack |
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|
Storage Temperature | +5 to +122 degrees Fahrenheit / |
|
|
Operating | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Temperature |
|
|
|