Output voltage regulation (Economy line mode)
+/- 10%
Output voltage regulation (Battery mode)
+/- 2%
Output AC waveform (AC mode)
Output AC waveform (battery mode)
INPUT
Pure Sine wave
Pure Sine wave
Rated input current (at maximum load)
Nominal Input Voltage(s) Supported
UPS input connection type
UPS input connection description
54A (208V), 46.8A (240V)
208V AC; 240V AC
Hardwire
3 wire single phase input (L1, L2, G)
Recommended Electrical Service
BATTERY
60A
Full load runtime (minutes)
Half load runtime (minutes)
Expandable battery runtime
External battery pack compatibility
DC system voltage (VDC)
Battery recharge rate (included batteries)
4.3min. (9000w)
12.5min. (4500w)
Supports extended runtime with optional external battery packs
BP240V10RT3U;
240
Less than 6 hours from 10% to 90%
Battery replacement description
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Undervoltage correction
2% output voltage regulation in standard online,
Corrects overvoltages up to 300V
Corrects undervoltages as low as 100V
LEDS ALARMS & SWITCHES
LED Indicators
6 LEDs indicate line power, online mode, economy/bypass mode,