Specifications

OUTPUT Maintains full-time sine wave output within 2% of 208/240 and 120V nominal at 50/60Hz during brownouts as low 100V and overvoltages as high as 300V

Output kVA capacity (kVA) Expandable runtime is supported with optional BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH external battery packs

Output kW capacity Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual) Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs

Frequency compatibility Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement

Output voltage regulation (line mode) PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto-shutdown of connected systems as UPS batteries become depleted

Manual background Includes Free PowerAlert monitoring software packages; PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA (Network Shutdown Agent) for larger networks and PowerAlert NMS (Network Management System) for monitoring up to 250 SNMP-enabled UPS, PDU and other networking devices

Manual background Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces

Manual background HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X

Manual background Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces

Manual background Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification

Manual background Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires removal of USB interface module)

Manual background Supports Emergency Power Off (EPO) via built-in interface

Manual background Included rail kit supports 9U 19 inch rackmount installation in 4 post racks

Manual background Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks

Manual background Front panel LEDs and LCD readout with scroll controls and password option supports visual monitoring of all major UPS functions and advanced UPS settings for charge level, nominal voltage selection, frequency conversion and other operational parameters

Manual background LED / LCD display panel rotates for viewing in rackmount or tower configurations

Manual background Network-grade AC surge and noise suppression

Manual background Industrial mode option (factory preset) enables supports high current startup loads by momentarily switching to bypass mode in response to short duration overload conditions

Manual background Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)

Manual background External battery packs are field replaceable and hot swappable

Specifications

OUTPUT

Output Volt Amp Capacity (VA)

Output kVA capacity (kVA)

Output Watt Capacity (watts)

Output kW capacity

Output power factor

Output Capacity Details

Nominal Output Voltage(s) Supported

Frequency compatibility

Frequency compatibility details

Output voltage regulation (line mode)

10000

10

9000

9.0

0.9

Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 95% or less

120V; 208V; 240V

50/60 Hz (auto-selectable)

Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz; Output frequency regulation +/- 0.05Hz (free running)

+/- 2%