Specifications

SYSTEM OVERVIEW True on-line, double-conversion UPS provides perfectly regulated sine wave output within 2% of 110/120V (user selectable) under all usage conditions

OUTPUT Maintains continuous operation through blackouts, voltage fluctuations and surges with zero transfer time

INPUT Removes harmonic distortion, fast electrical impulses, frequency variations and other hard to solve power problems not addressed by other UPS types

Manual background Corrects line voltage conditions as low as 65V and as high as 138V back to selectable 110/120V (+/-2%) values

Manual background Standard internal battery set offers 14 minutes runtime at half load (1200W) and 5 minutes at full load (2400W)

Manual background Optional BP72V28-3UNAFTA external battery packs offer expandable battery runtime

Manual background Space saving upright tower format

Manual background Fault tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS suffers internal failure and requires maintenance

Manual background Network interfaces support simultaneous communications via built-in USB, DB9 serial/contact-closure and SNMPWEBCARD slot

Manual background HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Manual background Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus any number of additional servers over IP

Manual background UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test, load bank output power control and remote reboot, UPS nominal voltage adjustment and UPS line to battery power voltage setpoints

Manual background Built-in Emergency Power Off (EPO) interface with cable

Manual background NEMA L5-30P input plug/NEMA 5-15/20R, L5-20R & L5-30R output receptacles

Manual background Integrated 2 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (each bank has four outlets)

Manual background Front panel LEDs offer current monitoring and battery charge level information

Manual background UPS ships fully assembled in full compliance with DOT regulations; no time consuming connection of internal batteries by user required

Manual background Single line TEL/DSL or network ethernet line surge suppression

Manual background 2 year manufacturer's product warranty; $250,000 Ultimate Lifetime Insurance

Specifications

SYSTEM OVERVIEW

Voltage

120V AC (110/120V)

compatibility

 

 

 

Frequency

50/60 Hz compatible (auto-sensing)

compatibility

 

 

 

OUTPUT

 

Output VA

3000

 

 

Output watts

2400

 

 

Output nominal

120V AC (110/120V)

voltage

 

 

 

Output voltage

Maintains full-time sine wave output within 2% of selected nominal, less than 3% total harmonic distortion (linear load) /

regulation

5% total harmonic distortion (computer load) (Less than 5% THD on-line and on-battery)

 

 

Output frequency

Regulates line frequency to 50/60Hz +/- 0.05Hz

regulation

 

 

 

Outlet quantity /

4 NEMA 5-15R, 4 NEMA 5-15/20R, 1 NEMA L5-30R

type

 

 

 

Customized load

2 controllable load banks support load shedding and remote reboot on demand of locked network devices (bank 1 has 4

management

outlets / bank 2 has 2 outlets)

receptacles

 

 

 

Overload

Via 40A input breaker

protection

 

 

 

INPUT

 

Maximum input

24A (120V) / 26.2A (110V)

amps

 

 

 

Input connection

NEMA L5-30P

type

 

 

 

Input cord length

10ft / 3m