Battery recharge rate

2-4 hours

 

 

VOLTAGE REGULATION

 

Voltage regulation

On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected

description

nominal voltage at all times

 

 

Overvoltage

Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within

correction

2% of selected nominal

 

 

Brownout correction

Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156VAC,

 

regulating output within 2% of selected nominal

 

 

LEDS ALARMS & SWITCHES

Front panel LEDs

Alarms

Switches

6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation.

Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete

Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions

SURGE / NOISE SUPPRESSION

AC surge suppression

480 joules

 

 

AC suppression

Instantaneous

response time

 

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight (lbs)

196

 

 

Shipping weight (kg)

89.1

 

 

Shipping Dimensions

25 x 40 x 48

(HWD/in)

 

 

 

Shipping Dimensions

63.5 x 101.6 x 121.9

(HWD/cm)

 

 

 

Unit weight (lbs)

Power Module: 42 lbs., Battery Pack: 92 lbs.

 

 

Unit weight (kg)

Power Module: 19.1kg, Battery Pack: 41.8kg

 

 

Unit Dimensions

Power Module: 5.25 x 17.5 x 26, Battery Pack: 3.5 x 17.5 x 22.5

(HWD/in)

 

 

 

Unit Dimensions

Power Module: 13.3 x 44.5 x 66 , Battery Pack: 8.9 x 44.5 x 57.2

(HWD/cm)

 

 

 

Material of

Steel

construction

 

 

 

Form factors

Rack (5U)

supported

 

 

 

Cooling method

Fan

 

 

ENVIRONMENTAL

 

Relative Humidity

0 to 95%, non-condensing

 

 

Storage Temperature

+5 to +122 degrees Fahrenheit

 

 

Operating

+32 to +104 degrees Fahrenheit

Temperature

 

 

 

Line mode BTU/hr.

1937.3

(Max.)

 

 

 

COMMUNICATIONS

 

Network monitoring

Includes 2 built-in DB9 monitoring ports (1-RS232 / 1-contact closure)

port

 

 

 

Software and cabling

Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Cabling

included

included.

 

 

SNMP compatibility

Built-in accessory slot accommodates internal SNMP / Web card and other network accessories

 

 