Tripp Lite SU5000RT4UTF 5000VA / 5kVA / 4500 watt
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Included rail kits support rackmount installation of both included modules in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (2 required for SU5000RT4UTF)
Optional
Maximum installed rack depth of only 20.75 in. / 52.7 cm
Maintains
Corrects brownouts to 156V at full load (100V at 50% load or less)
Corrects overvoltages to 290V at full load (300V at 90% load or less)
High efficiency ECONOMY MODE operation significantly reduces BTU heat output and operating energy costs
Supports detailed monitoring of equipment load levels,
UPS card slot supports one
RELAYIOCARD)
Optional SNMPWEBCARD offers communications and control via secure remote web and network interfaces
Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification
Optional RELAYIOMINI interface module offers three configurable hard contact closure outputs for custom event notification (requires removal of USB interface module)
Front panel LEDs and LCD readout with scroll controls support
LED/LCD display panel rotates for viewing in rackmount or tower configurations
Supports Emergency Power Off (EPO) via
Battery independent restart ensures automatic UPS
External battery packs are field replaceable and hot swappable
Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software (see manual) $250,000 connected equipment insurance;
Specifications
OUTPUT
Output Volt Amp Capacity (VA)
Output kVA capacity (kVA)
Output Watt Capacity (watts)
Output kW capacity
Output power factor
Crest Factor
Nominal Output Voltage(s) Supported
5000
5.0
4500
4.5
0.9
3:1
120V; 208V