Installed whole system maximum rack depth (inches)

20.75

Installed whole system maximum rack depth (cm)

52.7

Installed whole system total rack space height (rack spaces)

6U

Secondary form factor

UPS / Power Module weight (lbs)

UPS / Power Module weight (kg)

Stepdown transformer dimensions (height x width x depth / inches)

Stepdown transformer dimensions (height x width x depth / cm)

Stepdown transformer weight (lbs)

Stepdown transformer weight (kg)

UPS Shipping dimensions (height x width x depth / inches)

Tower

113.6

51.6

3.5x 17.5 x 20.75

8.8x 44.4 x 52.7

76

34.5

22 x 25 x 30

UPS Shipping

 

55.9 x 63.5 x 76.2

dimensions (height x

 

 

width x depth / cm)

 

 

 

 

 

 

 

Shipping weight (lbs)

278

 

 

 

 

 

Shipping weight (kg)

126.2

 

 

 

 

 

 

UPS housing material

 

Sheet metal

 

 

 

 

 

 

Cooling method

 

Fan

 

 

 

ENVIRONMENTAL

 

 

 

 

 

Operating

 

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Temperature Range

 

 

 

 

 

 

 

 

Storage Temperature

 

5 to 122 F / -15 to 50 C

Range

 

 

 

 

 

 

 

 

Relative Humidity

 

5% to 90% (non-condensing)

 

 

 

 

 

AC mode BTU / hr.

1767

(full load)

 

 

 

 

 

 

 

AC economy mode

638

BTU / hr. (full load)

 

 

 

 

 

 

 

Battery mode BTU /

1700

hr. (full load)

 

 

 

 

 

Page 5
Image 5
Tripp Lite SU5000RT4UTF manual Environmental