Tripp Lite SU8000RT3U Output voltage regulation line mode, Output voltage regulation Battery mode

Models: SU8000RT3U

1 7
Download 7 pages 11.04 Kb
Page 3
Image 3
Output voltage regulation (line mode)

Frequency compatibility details

Output voltage regulation (line mode)

Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)

+/- 2%

Output voltage regulation (Economy line mode)

+/- 10%

Output voltage regulation (Battery mode)

+/- 2%

Built-in UPS output receptacles

Output circuit breaker

Output AC waveform (AC mode)

Output AC waveform (battery mode)

INPUT

4 L6-20R outlet(s); 2 L6-30R outlet(s)

20A double-pole (x2) protects 2 L6-20R outlets each, 30A double-pole (x2) protects 1 L6-30R outlet each

Sine wave

Pure Sine wave

Rated input current (at maximum load)

Nominal Input Voltage(s) Supported

UPS input connection type

UPS input connection description

46A (200V), 44.2A (208V), 41.8A (220V), 40A (230V), 38.3A (240V)

200V AC; 208V AC; 220V AC; 230V AC; 240V AC

Hardwire

3 wire single phase input (L1, L2, G)

Recommended Electrical Service

BATTERY

50A

Full load runtime (minutes)

Half load runtime (minutes)

Expandable battery runtime

External battery pack compatibility

DC system voltage (VDC)

Battery recharge rate (included batteries)

5.5min. (7200w)

13.5min. (3600w)

Supports extended runtime with optional external battery packs

BP240V10RT3U; BP240V557C-1PH;BP240V787C-1PH;BP240V1037C-1PH;BP240V1407C-1PH

240

Less than 6 hours from 10% to 90%

Battery replacement description

Hot-swappable, user replaceable external battery packs

VOLTAGE REGULATION

Voltage regulation description

2% output voltage regulation in standard online, double-conversion mode

Page 3
Image 3
Tripp Lite SU8000RT3U Output voltage regulation line mode, Output voltage regulation Battery mode, Output circuit breaker