Half load runtime
Expandable battery runtime
Connects to UPS via
DC system voltage
Typical battery lifespan
Battery recharge rate
15 min. (4000VA/3200W)
Runtime is expandable with optional external battery packs
Included
240VDC
Less than 8 hours to 90% (included battery set only)
VOLTAGE REGULATION
Voltage regulation description
Overvoltage correction
Brownout correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within 2% of selected nominal
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC, regulating output within 2% of selected nominal
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
Switches
6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. LED/LCD display panel easily rotates for viewing in rackmount or tower configurations.
Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC suppression | Instantaneous |
response time |
|
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 331 |
|
|
Shipping weight (kg) | 150.3 |
|
|
Shipping | 39.75 x 31.5 x 23 |
Dimensions (HWD/in) |
|
|
|
Shipping | 101 x 80 x 58.4 |
Dimensions |
|
(HWD/cm) |
|
|
|
Unit weight (lbs) | Power Module 55 lbs., Battery Pack: 136.5 lbs. |
|
|
Unit weight (kg) | Power Module 25 kg., Battery Pack: 62 kg |
|
|
Unit Dimensions | Power Module 5.14 x 17.5 x 25, Battery Pack 5.16 x 17.5 x 25 (Installed depth of power module extends to 32.5 inches |
(HWD/in) | once detachable PDU backplate is installed) |
|
|
Unit Dimensions | Power Module 13.3 x 44.4 x 63.5, Battery Pack 13.4 x 40.6 x 63.5 (Installed depth of power module extends to 82.6 cm |
(HWD/cm) | once detachable PDU backplate is installed) |
|
|
Material of | Steel |
construction |
|
|
|
Form factors | Rack (6U) |
supported |
|
|
|
Cooling method | Fan |
|
|
Battery Access | User replaceable, hot swappable external battery pack |
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|
Storage Temperature
+5 to +122 degrees Fahrenheit