Tripp Lite SU8000RT3U1TF warranty Features, Specifications, System Overview, Output, Input

Models: SU8000RT3U1TF

1 5
Download 5 pages 8.79 Kb
Page 2
Image 2
Features

Package Includes

Specifications 3U power module with detachable hot-swap PDU input/output panel and bypass switch

SYSTEM OVERVIEW 3U external battery pack, 2U step-down transformer

OUTPUT Three sets of 4 post rackmount rails (one for each of the 2U and 3U components)

INPUT One set of tower stands for upright tower configuration

Manual background PowerAlert software, complete data cabling, user manual with warranty information

Features

Manual background 8,000 VA (8kVA) on-line, double-conversion UPS system (High voltage input/High AND low voltage output)

Manual background Detachable input-output PDU module with manual bypass switch enables hot-swap UPS replacement without powering off connected equipment

Manual background Installs in only 8 rack spaces (3U power module/3U battery pack/2U step-down transformer) with a maximum installed depth of 32.5 inches Manual background Offers 6 min. runtime at full load (8000VA/6400W) and 15 min. at half load (4000VA/3200W). Runtime is expandable with any number of optional external battery packs

Manual background Full-time sine wave 208V and simultaneous 120V +/-2% output

Manual background Actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output

Manual background Operates continuously without using battery power during brownouts to 156V and overvoltages to 276V

Manual background Standard 3-wire 208V hardwire input connection

Manual background 2 x NEMA L6-30R, 4 x L6-20R and 12 x 5-15/20R output receptacles

Manual background Detailed LCD panel with scroll buttons offers detailed diagnostic test

Manual background Network-grade AC surge and noise suppression

Manual background Zero transfer time between AC and battery operation

Manual background Includes slot for internal SNMP/web card, plus DB9 enhanced serial monitoring port, and contact closure port for unattended shudown, remote control and monitoring of UPS system and power data

Manual background Supports detailed monitoring of equipment load levels, self-test data and mains power conditions via network interfaces. Includes PowerAlert monitoring software and complete cabling

Manual background Emergency Power Off (EPO) interface

Manual background Front panel LEDs offer at-a-glance confirmation of line power status, battery power status, AC-to-DC & DC-to-AC conversion, bypass mode and output power status.

Manual background Fault-tolerant auto-bypass mode prevents loss of output during UPS fault conditions or excessive UPS loading

Manual background 4 post rackmount and upright tower installation accessories included. 2POSTRMKITWM two post rackmount hardware accessories available

Manual background Field replaceable, hot swappable power module and external battery packs

Manual background Attractive all-black color scheme

Manual background2-year warranty: $250,000 connected equipment insurance Manual background Extended warranty and service contracts available

Specifications

SYSTEM OVERVIEW

Voltage compatibility

208V & 120V AC

 

 

Frequency

50/60 Hz

compatibility

 

 

 

OUTPUT

 

Output VA

8000

 

 

Output watts

6400

 

 

Output nominal

208V & 120V AC

voltage

 

 

 

Output voltage

Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 3% total

regulation

harmonic distortion when used with computer loads

 

 

Output frequency

Regulates line frequency to 50/60Hz +/- 0.05Hz

regulation

 

 

 

Outlet quantity / type

4 NEMA L6-20R, 2 NEMA L6-30R, 12 NEMA 5-15/20R

 

 

INPUT

 

Maximum input amps

208V - 36A

 

 

Page 2
Image 2