Tripp Lite SU8000RT3UN50TF Battery, Leds Alarms & Switches, Surge / Noise Suppression, Physical

Models: SU8000RT3UN50TF

1 5
Download 5 pages 7.53 Kb
Page 3
Image 3
BATTERY

Input cord length

10 ft. / 3.05 meters

 

 

Recommended

208V 50A circuit with either a 50A Hubbell CS8264C female connector or CS8269 wall receptacle

Electrical Service

 

 

 

BATTERY

 

Full load runtime

6 min. (8000VA/6400W)

 

 

Half load runtime

15 min. (4000VA/3200W)

 

 

Expandable battery

Expandable with optional external battery packs

runtime

 

 

 

Connects to UPS via

Included 3 wire DC cable

 

 

DC system voltage

240VDC

 

 

Typical battery

4-6 years

lifespan

 

 

 

Battery recharge rate

Less than 8 hours to 90% (included battery set only)

 

 

VOLTAGE REGULATION

 

Voltage regulation

On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected

description

nominal voltage at all times

 

 

Overvoltage

Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within

correction

2% of selected nominal

 

 

Brownout correction

Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC,

 

regulating output within 2% of selected nominal

 

 

LEDS ALARMS & SWITCHES

Front panel LEDs

Alarms

Switches

6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. LED/LCD display panel easily rotates for viewing in rackmount or tower configurations.

Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete

Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions

SURGE / NOISE SUPPRESSION

AC suppression

Instantaneous

response time

 

 

 

EMI / RFI AC noise

Yes

suppression

 

 

 

PHYSICAL

 

Shipping weight (lbs)

402

 

 

Shipping weight (kg)

181

 

 

Shipping Dimensions

49.25 x 31.5 x 23

(HWD/in)

 

 

 

Shipping Dimensions

125.1 x 80 x 58.4

(HWD/cm)

 

 

 

Unit weight (lbs)

Power Module 55 lbs., Battery Pack: 136.5 lbs., Step-down transformer: 57 lbs.

 

 

Unit weight (kg)

Power Module 25 kg., Battery Pack: 62 kg, Step down transformer: 25.9 lbs.

 

 

Unit Dimensions

Power Module 5.14 x 17.5 x 25, Battery Pack 5.14 x 17.5 x 25, Step down transformer 3.5 x 17.5 x 20.75 (Installed

(HWD/in)

depth of power module extends to 32.5 inches once detachable PDU backplate is installed)

 

 

Unit Dimensions

Power Module 13.3 x 44.4 x 63.5, Battery Pack 13.4 x 40.6 x 63.5, Step down transformer 8.9 x 40.6 x 52.7 (Installed

(HWD/cm)

depth of power module extends to 82.6 cm once detachable PDU backplate is installed)

 

 

Material of

Steel

construction

 

 

 

Form factors

Rack (8U)

supported

 

 

 

Cooling method

Fan

Page 3
Image 3
Tripp Lite SU8000RT3UN50TF warranty Battery, Leds Alarms & Switches, Surge / Noise Suppression, Physical