6Power ON UPS system 1, being sure that the output breakers are OFF.

Connection

In order to make connections between 2 UPS systems in parallel, two 6kVA UPS systems, the primary detachable PDU module and the secondary PDU module will be needed.

1Being sure that all switches are off and all units are powered down, refer back to the

“Mounting” section of the manual. First, mount the UPS systems and then the primary and secondary parallel PDUs.

2Originating from the secondary PDU interconnect port A , connect the parallel power interconnect cable B to the primary PDU C as seen in diagram 2.

C

B

A

2

3 Connect the 2 parallel cables. Both will originate from the primary parallel PDU with 1 connecting to UPS system 1 and the other to UPS system 2. (Refer to diagram 3.)

3

4Connect the hardwired input and output AC power connections (L1, L2 and Ground wires) to the primary PDU, according to the markings on the connectors. The AC input wiring attaches to the facility’s AC source while the AC output wiring connects to the intended equipment.

 

 

Maximum Rated

Maximum Rated

Typical

Model

Input Voltage

Input Current

Output Current

Wire Size

 

 

 

 

 

SUPDMB12KHW

200~240V (L-N)

60A

60A

8mm2

 

 

 

 

 

5With all switches in the OFF position, turn ON both the input breakers on the primary and secondary PDUs. Leave switches for the output breakers in the OFF position.

6Power ON UPS system 1, being sure that the output breakers are OFF.

7After UPS system 1 start-up is complete, power ON UPS system 2. The UPS systems will self detect the Parallel Mode and show the following screen shots for the primary and secondary

UPS systems:

PARALLEL: MASTER

 

PARALLEL: SLAVE

V00 CV01

 

V00

CV01

 

 

 

 

When the unit is in Parallel Mode UPS system 1 will display “Parallel: Master” and UPS

system 2 will display “Parallel: Slave”.

8Once Parallel Mode is detected, turn on both output breakers for the primary and secondary PDUs.