Connection
In order to make connections between 2 UPS systems in parallel, two 6kVA UPS systems, the primary detachable PDU module and the secondary PDU module will be needed.
1Being sure that all switches are off and all units are powered down, refer back to the
“Mounting” section of the manual. First, mount the UPS systems and then the primary and secondary parallel PDUs.
2Originating from the secondary PDU interconnect port A , connect the parallel power interconnect cable B to the primary PDU C as seen in diagram 2.
C |
B |
A |
2 |
3 Connect the 2 parallel cables. Both will originate from the primary parallel PDU with 1 connecting to UPS system 1 and the other to UPS system 2. (Refer to diagram 3.)
3
4Connect the hardwired input and output AC power connections (L1, L2 and Ground wires) to the primary PDU, according to the markings on the connectors. The AC input wiring attaches to the facility’s AC source while the AC output wiring connects to the intended equipment.
|
| Maximum Rated | Maximum Rated | Typical |
Model | Input Voltage | Input Current | Output Current | Wire Size |
|
|
|
|
|
SUPDMB12KHW | 200~240V | 60A | 60A | 8mm2 |
|
|
|
|
|
5With all switches in the OFF position, turn ON both the input breakers on the primary and secondary PDUs. Leave switches for the output breakers in the OFF position.
6Power ON UPS system 1, being sure that the output breakers are OFF.
7After UPS system 1
UPS systems:
PARALLEL: MASTER |
| PARALLEL: SLAVE | |
V00 CV01 |
| V00 | CV01 |
|
|
|
|
When the unit is in Parallel Mode UPS system 1 will display “Parallel: Master” and UPS
system 2 will display “Parallel: Slave”.
8Once Parallel Mode is detected, turn on both output breakers for the primary and secondary PDUs.