AC suppression | Instantaneous |
response time |
|
|
|
Dataline suppression | - |
|
|
EMI / RFI AC noise | Yes |
suppression |
|
|
|
PHYSICAL |
|
Shipping weight (lbs) | 39 |
|
|
Shipping weight (kg) | 17.7 |
|
|
Unit weight (lbs) | 36.5 |
|
|
Unit weight (kg) | 16.6 |
|
|
Unit Dimensions | 12.75 x 7.5 x 9 |
(HWD/in) |
|
|
|
Unit Dimensions | 32.4 x 19.1 x 22.9 |
(HWD/cm) |
|
|
|
Material of | PVC |
construction |
|
|
|
Form factors | Tower |
supported |
|
|
|
Cooling method | Convection |
|
|
Battery Access | Battery access door allows user replacement of UPS batteries |
|
|
ENVIRONMENTAL |
|
Relative Humidity | 0 to 95%, |
|
|
Storage Temperature | +5 to +122 degrees Fahrenheit, |
|
|
Operating | +32 to +104 degrees Fahrenheit, 0 to +40 degrees Celsius |
Temperature |
|
|
|
COMMUNICATIONS |
|
Network monitoring | DB9 |
port |
|
|
|
Software and cabling | PowerAlert software available for free download at www.tripplite.com |
included |
|
|
|
LINE / BATTERY TRANSFER
Transfer time from line power to battery mode
Low voltage transfer | Switches to battery power as line voltage decreases to 75 volts or less. Resets back to line power mode as line |
to battery power | voltage increases to 79V or higher. |
|
|
High voltage transfer | Switches to battery power as line voltage increases to 147 volts or higher. Resets back to line power mode as line |
to battery power | voltage decreases to 143V or less. |
|
|
SPECIAL FEATURES |
|
Cold Start | Yes, inverter can be "cold started" to enable temporary AC output during a power failure |
|
|
Appearance | Attractive gray tower UPS |
|
|
CERTIFICATIONS |
|
Certifications | Tested to UL1778 (USA), cUL (Canada), Class B (emissions), NOM (Mexico) |
|
|
WARRANTY |
|
Product Warranty | 2 year product warranty |
Period |
|
|
|
Connected | $200,000 connected equipment insurance (USA and Canada only) |
Equipment Coverage |
|
|
|
Optional Coverage | |
| information. |
|
|