Specifications
SYSTEM OVERVIEW
Voltage compatibility | 120V AC |
|
|
Frequency60Hz compatibility
OUTPUT
Output VA
Output watts
Output nominal voltage
Output voltage regulation
Output frequency regulation
Outlet quantity / type
INPUT
1200
940
120V AC
LINE MODE: Sine wave line voltage 120V
BATTERY MODE: PWM sine wave output 120V
LINE MODE: Passes line frequency of 60Hz
BATTERY MODE: Inverter output regulated to 60Hz
6 NEMA
Maximum input amps
Input connection type
Input cord length
Recommended Electrical Service
BATTERY
8.25A / 990 watts
NEMA
6 ft., 14 gauge
15A 120V
Full load runtime
Half load runtime
DC system voltage
Typical battery lifespan
7 minutes (1200VA)
16 minutes (600VA)
36 VDC
Battery recharge rate
Replacement Battery | RBC53 |
Cartridge |
|
|
|
VOLTAGE REGULATION |
|
Voltage regulation | Automatic Voltage Regulation (AVR) circuits maintain clean, regulated |
description | using battery power, during brownouts to 75V and overvoltages to 147V |
|
|
Overvoltage | Input voltages between 128 and 147V AC are reduced by 12% |
correction |
|
|
|
Direct pass through | Input voltages between 108 and 127V AC are passed on to connected equipment unchanged |
|
|
Brownout correction | Input voltages between 93 and 107V AC are boosted by 14% |
|
|
Severe brownout | Input voltages between 75 and 92V AC are boosted by 30% |
correction |
|
|
|
LEDS ALARMS & SWITCHES
Front panel LEDs
Alarms
5 front panel LEDs indicate line power status, battery power status, battery low/replace status, voltage regulation operation and overload status
Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will
Switches
Includes 2 front panel switches — one main on/off power switch and one dual function "alarm cancel" / "self test" button
SURGE / NOISE SUPPRESSION
AC surge suppression 480 joules