Notes

1.No code stamp or ‘NB’ on nameplate below 1.1 barg set.

2.Pressure Limitations

Model 910, 916: 0.2 to 62 barg

Model 911, 917: 0.2 to 62 barg

Model 912, 918: 0.2 to 20.7 barg

Model 913, 919: 0.2 to 62 barg

Kunkle Safety and Relief Products

Models 910, 911, 912, 913, 916, 917, 918, 919, 920, 921 and 927

Models 910, 911, 912, 913, 916, 917, 918, 919

Non-code1and ASME Section VIII Liquid, [Metric m3/h] -

Flow Coefficient = 0.710

Set Pressure

———––——————Orifice Area, cm2

—————–————

[barg]

D

E

F

G

H

J

 

[0.783]

[1.392]

[2.174]

[3.568]

[5.574]

[9.129]

 

 

 

 

 

 

 

1.0

3

6

9

14

22

36

 

 

 

 

 

 

 

2.0

4

7

12

19

30

49

3.0

5

9

14

23

37

60

 

 

 

 

 

 

 

4.0

6

11

16

27

42

69

5.0

7

12

18

30

47

77

 

 

 

 

 

 

 

6.0

7

13

20

33

52

85

7.0

8

14

22

36

56

92

 

 

 

 

 

 

 

8.0

8

15

23

38

60

98

9.0

9

16

25

41

63

104

 

 

 

 

 

 

 

10.0

9

17

26

43

67

110

12.0

10

18

29

47

73

120

 

 

 

 

 

 

 

14.0

11

20

31

51

79

130

16.0

12

21

33

54

85

139

 

 

 

 

 

 

 

18.0

13

22

35

57

90

147

20.0

13

24

37

61

95

155

 

 

 

 

 

 

 

22.0

14

25

39

63

99

162

24.0

15

26

40

66

104

170

 

 

 

 

 

 

 

26.0

15

27

42

69

108

177

28.0

16

28

44

72

112

183

 

 

 

 

 

 

 

30.0

16

29

45

74

116

190

32.0

17

30

47

77

120

196

 

 

 

 

 

 

 

34.0

17

31

48

79

123

202

36.0

18

32

49

81

 

 

 

 

 

 

 

38.0

18

33

51

83

40.0

19

33

52

86

 

 

 

 

 

 

 

42.0

19

34

44.0

20

35

 

 

 

 

 

 

 

46.0

20

36

48.0

21

37

 

 

 

 

 

 

 

50.0

21

37

52.0

21

38

 

 

 

 

 

 

 

54.0

22

39

56.0

22

40

 

 

 

 

 

 

 

58.0

23

40

60.0

23

41

 

 

 

 

 

 

 

62.0

23

42

Tyco reserves the right to change product design and specifications

KUKMC-0392

without notice. Copyright © 2002 by Tyco International Ltd.

19