Note

1.Pressure Limitations

Models 910, 916: 0.2 to 62 barg

Models 911, 917: 0.2 to 62 barg

Models 912, 918: 0.2 to 20.7 barg

Models 913, 919: 0.2 to 62 barg

Kunkle Safety and Relief Products

Models 910, 911, 912, 913, 916, 917, 918, 919, 920, 921 and 927

Models 910, 911, 912, 913, 916, 917, 918, 919

Non-code Liquid - 25% Accumulation, [Metric, m3/h]

Flow Coefficient = 0.710

Set Pressure

———–——————Orifice Area, cm2

——––—––—————

[barg]

D

E

F

G

H

J

 

[0.783]

[1.392]

[2.174]

[3.568]

[5.574]

[9.129]

 

 

 

 

 

 

 

0.2

1

3

4

6

10

17

 

 

 

 

 

 

 

0.5

2

4

6

10

16

26

1.0

3

6

9

14

23

37

 

 

 

 

 

 

 

2.0

4

8

12

20

32

52

3.0

5

10

15

25

39

64

 

 

 

 

 

 

 

4.0

6

11

18

29

45

74

5.0

7

13

20

32

50

83

 

 

 

 

 

 

 

6.0

8

14

22

35

55

90

7.0

8

15

23

38

60

98

 

 

 

 

 

 

 

8.0

9

16

25

41

64

104

9.0

9

17

26

43

68

111

 

 

 

 

 

 

 

10.0

10

18

28

46

71

117

12.0

11

19

30

50

78

128

 

 

 

 

 

 

 

14.0

12

21

33

54

84

138

16.0

13

23

35

58

90

148

 

 

 

 

 

 

 

18.0

13

24

37

61

96

157

20.0

14

25

39

65

101

165

 

 

 

 

 

 

 

22.0

15

26

41

68

106

173

24.0

16

28

43

71

110

181

 

 

 

 

 

 

 

26.0

16

29

45

74

115

188

28.0

17

30

47

76

119

195

 

 

 

 

 

 

 

30.0

17

31

48

79

123

202

32.0

18

32

50

82

128

209

 

 

 

 

 

 

 

34.0

18

33

51

84

131

215

36.0

19

34

53

87

 

 

 

 

 

 

 

38.0

20

35

54

89

40.0

20

36

56

91

 

 

 

 

 

 

 

42.0

21

36

44.0

21

37

 

 

 

 

 

 

 

46.0

21

38

48.0

22

39

 

 

 

 

 

 

 

50.0

22

40

52.0

23

41

 

 

 

 

 

 

 

54.0

23

41

56.0

24

42

 

 

 

 

 

 

 

58.0

24

43

60.0

25

44

 

 

 

 

 

 

 

62.0

25

44

Tyco reserves the right to change product design and specifications

KUKMC-0392

without notice. Copyright © 2002 by Tyco International Ltd.

21