Kunkle Safety and Relief Products

Models 910, 911, 912, 913, 916, 917, 918, 919, 920, 921 and 927

Models 910, 911, 912, 913, 916, 917, 918, 919

Non-code Vacuum Air [Metric, Nm3/h] - Flow Coefficient = 0.878

Set Pressure

————––—————Orifice Area, cm2

——————–———

[mbarg]

D

E

F

G

H

J

 

[0.7826]

[1.3916]

[2.1735]

[3.5677]

[5.574]

[9.129]

 

 

 

 

 

 

 

200

40

71

111

182

285

466

 

 

 

 

 

 

 

225

42

74

115

189

296

485

250

43

76

119

196

306

501

 

 

 

 

 

 

 

275

44

78

123

201

314

515

300

45

80

125

206

321

526

 

 

 

 

 

 

 

325

46

82

127

209

327

535

350

46

83

129

212

331

542

 

 

 

 

 

 

 

375

47

83

130

214

334

548

400

47

84

131

215

336

551

 

 

 

 

 

 

 

425

47

84

132

216

337

553

450

47

84

132

216

337

552

 

 

 

 

 

 

 

475

47

84

132

216

338

553

500

47

84

132

216

338

553

 

 

 

 

 

 

 

525

47

84

132

216

338

553

550

47

84

132

216

338

553

 

 

 

 

 

 

 

575

47

84

132

216

338

553

600

47

84

132

216

338

553

 

 

 

 

 

 

 

625

47

84

132

216

338

553

650

47

84

132

216

338

553

 

 

 

 

 

 

 

675

47

84

132

216

338

553

700

47

84

132

216

338

553

 

 

 

 

 

 

 

725

47

84

132

216

338

553

750

47

84

132

216

338

553

 

 

 

 

 

 

 

775

47

84

132

216

338

553

800

47

84

132

216

338

553

 

 

 

 

 

 

 

845

47

84

132

216

338

553

850

47

84

132

216

338

553

 

 

 

 

 

 

 

875

47

84

132

216

338

553

900

47

84

132

216

338

553

 

 

 

 

 

 

 

925

47

84

132

216

338

553

950

47

84

132

216

338

553

 

 

 

 

 

 

 

975

47

84

132

216

338

553

1000

47

84

132

216

338

553

 

 

 

 

 

 

 

Tyco reserves the right to change product design and specifications

KUKMC-0392

without notice. Copyright © 2002 by Tyco International Ltd.

23