Tyco DIU 210 manual Technical Specifications, Product Highlights, Interfaces, Board Protection

Models: DIU 210

1 2
Download 2 pages 41.54 Kb
Page 2
Image 2
Product Highlights

CEM/B/045

Product Highlights

Interfaces

The DIU 210 provides direct interfaces to the following devices:

CEM Card Reader

Electric Door Lock

Fire Alarm System

Break Glass Unit

Exit Push Button

Inputs from alarm devices

Up to 8 inputs can be wired from alarm/status monitoring devices directly to the DIU 210. These devices are used to monitor door sensors, DIU tamper and battery alarms and fire/ break glass emergency conditions.

If an input from the fire alarm system or break glass unit changes state, the power to the door lock is automatically dropped; this hardware-controlled facility ensures that the door opens in an emergency situation. Details of alarm conditions

can be sent directly to the door controller or to the host, via the card reader, for central alarm notification.

Board Protection

The DIU 210 has been designed to meet the UL294 standard providing resistance to power supply tamper, limiting the current to a reader so that shorting together the 12 Volt terminals prevents the lock from opening.

Reader Inputs

The DIU 210 can also monitor the status of all the door furniture inputs, freeing up the inputs on the intelligent CEM reader for general purpose input monitoring.

PSU Backplane Board and Enclosure

The DIU 210 is supplied with a steel enclosure and backplane board providing a mains input PSU, battery charging capabilities and door holder connections.

TECHNICAL SPECIFICATIONS

Physical

 

 

 

Size

300 x 250 x 150 mm

 

Battery Low (reported internally)

 

(11.8 x 9.84 x 5.9in)

 

Dedicated Power Fail Input

 

 

 

* = 4 state tamper protected inputs

Weight

4.3Kg

Outputs

Three 12V or 24V open collector outputs

Power

 

- Voltage

100-240VAC, 50/60Hz

 

limited to 1.5A

 

Current 0.6A (excluding locks and heads)

 

(Door Lock, Door Holder and External

 

Consumption

 

Sounder)

Environmental

 

Reader Output

12V, limited to 800mA

- Temperature

-10º to 40ºC (14º to 104ºF)

Memory

32kB Flash memory

- Humidity

95% non condensing

LED Indicators

+12 Volts OK, Lock supply OK, Lock Status,

Communication Interface

 

Watchdog, Fault, Battery Low, RS485 Rx

To Card Reader

RS485 multidrop cable runs using copper

 

and TX.

 

 

 

wire with maximum length of 1.2km

Functionality

 

 

without repeater

 

 

- Connection

2 part screw terminals

Inputs

* Door Position

Product Codes

 

 

* Lock Status

 

 

* Exit Push Button

DIU/700/000

DIU 210 (Complete with PSU Backplane

 

* General Purpose

 

Break Glass Sense

 

and Enclosure.

Fire Alarm Sense

Power Fail

Tamper

Product specifications and availability is subject to change without notice. Certain product names mentioned herein may be trade names and/or registered trademarks of their companies.

CEM Systems Ltd Unit 4 Ravenhill Business Park Ravenhill Road Belfast BT6 8AW Northern Ireland

www.cemsys.com

Tel: +44 (0)28 9045 6767 Fax: +44 (0)28 9045 4535 email: cem.sales@tycoint.com