Installation Instructions

TYPES OF SYSTEMS

This manual covers three of the basic types of systems offered by Avtec:

 

 

 

 

TAKU-Baffle Filter (AF)

 

 

• Modular Grease Extractor (AX)

 

• Auto Wash Down (AW)

 

 

BAFFLE FILTER (AF) SERIES

 

Model AF ventilators are listed by UL and are built in accordance of NFPA-96 for use

 

with UL listed

re extinguishing systems for duct hood protection. They are available

 

with or without an automatic

re damper. They utilize UL classified removable baffle

 

filters to extract grease and provide a limited re barrier. The canopy contains a hidden

 

grease trough and removable cup. Surface, plenum and duct collar re extinguishing

 

systems may be factory supplied.

 

MODULAR GREASE EXTRACTORS (AX) SERIES

 

Model AX ventilators are listed by UL and are built in accordance of NFPA-96 for use

 

with UL listed

re extinguishing systems for duct hood protection. They are available

 

with or without an automatic

re damper. These models utilize high velocity removable

grease extractors. The canopy contains a hidden grease trough and removable cup. Sur- face, plenum and duct collar re extinguishing systems may be factory supplied.

AUTO WASH DOWN (AW) SERIES

Model AW ventilators are listed by UL and are built in accordance of NFPA-96 for use with UL listed re extinguishing systems for duct hood protection. They are available with or without an automatic re damper. These systems utilize a high velocity grease extractor and an integral water wash system cleans the inside of the grease extraction chamber either by manual activation of the Wash Start button or by a programmable timer. The duration of the wash is electronically controlled. The wash system is also activated by an electrical thermostat or a manual switch in the event of a re condition. A surface re extinguishing system is required and may be factory supplied.