DESIGN GUIDELINES FOR 6041I INSERT INSTALLATION

4” VENT IS MANDA-

TORY FOR INSERT

INSTALLATIONS.

4” VENT IS MANDA-

TORY FOR INSERT

INSTALLATIONS.

INSTALLATION INTO A MASONRY FIREPLACE

When installing into a masonry fireplace, DO NOT remove any bricks or masonry, with the following exception: masonry or steel, including the damper plate, may be removed from the smoke shelf and adjacent damper frame, if necessary, to accommo- date a chimney liner. Do this only if their removal will not weaken the structure of the fireplace or the chimney, and will not reduce protection for combustibles to less than that required by national building codes.

Installation must include a chimney liner (4” Pell Vent “PL” Piping) that extends the full height of the chimney and meets type HT requirements. The liner must be securely attached to the insert and the chimney top. The chimney must be sealed either at the top or at the damper area with a non- combustible plate to prevent room air passage to chimney cavity.

Outside combustion air may be drawn through the chimney top or through an existing ash cleanout.

INSTALLATION INTO A FACTORY-BUILT

(METAL) FIREPLACE

When installing into a zero clearance fireplace, The firebox must accept the insert without modification other than removing bolted or screwed together pieces such as smoke shelf/deflectors, ash lips, screen or door tracks, and damper assemblies. These items must be re-installed if the insert is removed and not replaced. The removal of any part must not alter the integrity of the listed fire- place in any way.

The factory built fireplace must be listed per UL

127.Installation must include a chimney liner (4” Pell Vent “PL” Piping) that extends the full height of the chimney and meets type HT requirements. The liner must be securely attached to the insert and the chimney top. The chimney must be sealed either at the top or at the damper area with a non- combustible plate to prevent room air passage to chimney cavity.

For raised hearth installations, adjust the leveling bolts under the front of the unit.

16

USSC

Page 16
Image 16
United States Stove 6041TP, 6041I Installation Into a Masonry Fireplace, Installation Into a FACTORY-BUILT Metal Fireplace