Pressure Testing Heater Gas Connections

VANGUARD FLAME-MAX®

UNVENTED PROPANE/LP GAS LOG HEATER

INSTALLATION

Continued

A.G.A. Design-Certified Manual

Shutoff Valve With 1/8" NPT Tap*

Approved Flexible Gas Hose (if allowed by local codes)

Gas Control

3" Minimum CHECKING GASPressure Testing Gas Supply Piping SystemManual background

From External

Regulator (11"

W.C.** to 14"

W.C. Pressure)

Tee Joint

Sediment

Pipe Nipple

Cap

Trap

 

 

 

Pressure Testing Heater Gas Connections

1.Open manual shutoff valve (see Fig- ure 15).

2.Open propane supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to control valve (see Figure 16). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 14 through 16 ). Check all other internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 15).

Figure 14 - Gas Connection

*Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 24.

**Minimum inlet pressure for purpose of input adjustment.

Open

Manual

Shutoff Manual background

Valve

CHECKING GAS

CONNECTIONS

Manual background WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

Manual background WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Manual background CAUTION: Make sure exter- nal regulator has been installed between propane supply and heater. See guidelines under Con- necting to Gas Supply, page 11.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG

1.Disconnect heater and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

3.Pressurize supply piping system by ei- ther using compressed air or opening propane supply tank valve.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Reconnect heater and manual shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Fig- ure 15).

2.Pressurize supply piping system by ei- ther using compressed air or opening propane supply tank valve.

3.Check all joints from propane supply tank to manual shutoff valve (see Fig- ure 16). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

4.Correct all leaks at once.

 

Closed

Figure 15 - Manual Shutoff Valve

Propane

Manual Shutoff Valve

Supply

 

Tank

 

 

Control Valve

 

Location

Figure 16 - Checking Gas Joints