Determining Minimum Mantel Clearance

OWNER’S MANUAL

INSTALLATION

Continued

MANTEL CLEARANCES

In addition to meeting noncombustible ma- terial clearances, you must also meet re- quired clearances between fireplace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).

Determining Minimum Mantel Clearance When Using a Hood

If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clear- ances shown in Figure 7 when using hood.

 

 

 

10"

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

 

 

Underside of

 

 

 

8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel Shelf

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 1/2"

 

 

 

 

 

 

All minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

distances are

Minimum Non-

 

 

(A)

 

 

 

 

 

 

in inches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Combustible

 

 

 

 

 

 

 

 

Log Set

 

 

 

 

 

 

 

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

12"

18"

 

20"

22"

24"

 

24"/30"/36" Models

 

 

 

 

 

 

 

 

 

 

 

 

8"

8"

 

14"

163/4"

20"

 

18" Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of Fireplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Opening

 

 

 

 

Minimum Non-

Distances to

 

 

 

 

 

 

 

Combustible

 

Underside of

 

 

 

 

 

 

 

Material Height

Mantel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 6 - Minimum Mantel Clearances Without Using Hood

Mantel Shelf

NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:

operate the logs only with the flue damper open

raise the mantel to an accept- able height

remove the mantel

FLOOR CLEARANCES

12"

10"

8"

6"

2 1/2"

Minimum Non-

Combustible

Material

8"

Min.

12"

15"

18"

Underside of

Mantel Shelf

All minimum distances are in inches

Log Sets

20"Log Set All Models

Top of Fireplace Opening

A. If installing appliance on the floor level,

Hood

Distances to

(GA6050, GA6052,

you must maintain the minimum dis-

tance of 14" to combustibles (see Fig-

ure 8).

B. If combustible materials are less than

or GA6053)

Underside of Mantel

14" to the fireplace, you must install

appliance at least 5" above the combus-

tible flooring (see Figure 9).

Figure 7 - Minimum Mantel Clearances When Using Hood

Combustible

Hearth
Combustible
14" Material

Min.

 

Material

 

 

5"

 

 

Min.

Noncombustible Material
Figure 9 - Minimum Fireplace Clearances
Figure 8 - Minimum Fireplace Clearances
Above Combustible Flooring
If Installed at Floor Level

 

Continued

 

 