Fig. 14 Extra floor protection may be required for the fire- place hearth, even if your stove is installed with the legs and the bottom heat shield.
Fireplace Installation Clearances
A fireplace installation requires special clearance be- tween the:
•Side of the stove and the right and left walls
•Side of the stove and the decorative side trim on the fireplace face
•Top of the stove and the mantel
In addition, both Fireplace Adaptor and Fireplace Insert installations have special floor protection requirements that are addressed in the section on Floor Protection.
|
| Dutchwest | |
|
| M |
|
|
| M |
|
|
| T |
|
S |
|
|
|
|
|
| ST426 |
Model: | 2460 | 2461 | 2462 |
Side Walls (S) | 20” (510mm) | 24” (610mm) | 23” (580mm) |
Trim (T) | 12” (300mm) | 12” (300mm) | 12” (30mm) |
Mantel (M) | 20” (510mm) | 20” (510mm) | 20” (510mm) |
Fig. 15 Minimum clearances for fireplace installation. Recom- mended clearances must be maintained between stove and the surrounding combustible components.