Vermont Casting 2478CE Wall Pass-Throughs, Hearths, Dutchwest Non-CatalyticConvection Heater

Models: 2478CE

1 28
Download 28 pages 49.35 Kb
Page 8
Image 8
Wall Pass-Throughs

Dutchwest Non-Catalytic Convection Heater

Flue Liner

 

Extend Chimney Con-

 

nector to the First Tile of

Damper

the Flue Liner

Plate is

 

Removed

 

or Locked

Observe

in Open

Position

Miniumum Clearances

 

 

Close Off

 

the Damper

 

Opening with

ST797

Sheet Metal

and Sealant

Fig. 8 The connector passes through the fireplace to enter flue. Special Fireplace Adapter Kits to simplify fireplace instal- lations are available from your local dealer.

Wall Pass-Throughs

Whenever possible, design your installation so the con- nector does not pass through a combustible wall. If you must use a wall pass-through in your installation, check with your building inspector before you begin and con- struct it in accordance with local building codes. Also check with the chimney connector manufacturer for any specific requirements.

Accessories are available for use as wall pass- throughs. If using one of these, make sure it has been tested and listed for use as a wall pass-through. Figure 9 shows one method of passing a connector through a wall. All combustible material in the wall is cut away to provide the required 460 mm (18”) clearance for the connector. The resulting space must remain empty.

A flush-mounted sheet metal cover may be used on one side only. If covers must be used on both sides, each cover must be mounted on non-combustible spacers at least 25 mm (1”) clear of the wall. Your Dutchwest deal-

er or your local building inspector can provide details of other approved methods of passing a chimney connec- tor through a combustible wall.

DO NOT CONNECT THE HEATER TO ANY AIR DIS- TRIBUTION DUCT OR SYSTEM.

460 mm (18”) Empty

 

Space All Around the

Sheet Metal

Chimney Connector

 

Cover

 

(One side

 

only)

ST421

Fig. 9 Hollow wall pass-through.

Hearths

This appliance must be installed on to hearth that meets the requirements of Part J of the Building Regu- lations 2000 (Combustion Appliances and Fuel Storage Systems). This can be achieved by ensuring that the hearth is constructed and sized in accordance with the guidelines included in section 2 of approved document ‘J’. The size and clearances of the hearth are as fol- lows:

The constructed hearth should be constructed in ac- cordance with the recommendations in document J, and should be of minimum width 840 mm and minimum depth 840 mm (if a free standing hearth b) above) or a minimum projection of 150 mm from the jamb (if a recessed hearth a) above).

 

 

 

 

 

 

 

 

Costructional Hearth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions as below

 

 

 

 

 

 

 

 

 

At least 150 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or to a suitable

 

 

 

 

 

Appliance

 

 

 

 

 

 

 

 

 

 

 

heat resistant wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Appliance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Doors

 

 

Doors

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hearth Surface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

At least

 

 

 

 

 

Free of Com-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bustible Material

 

 

 

 

 

 

 

 

 

 

 

 

150 mm

 

 

 

 

 

 

 

 

Perimeter should be

 

 

 

 

 

 

 

 

 

Perimeter should be

 

 

 

 

 

clearly marked e.g.

 

clearly marked e.g.

 

At least

edge of superimposed

 

edge of superimposed

 

hearth

 

 

 

 

hearth

 

300 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a) Fireplace recess

 

 

b) Free standing

 

 

ST912

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 10 Noncombustible hearth surface dimensions.

 

 

 

 

 

 

 

 

 

 

 

 

8

30003850

Page 8
Image 8
Vermont Casting 2478CE manual Wall Pass-Throughs, Hearths, Dutchwest Non-CatalyticConvection Heater, 30003850