Vermont Casting 647 BFC Canadian Requirements for Insulation Shield, Additional Ceilings, 7412647

Models: 647 BFC

1 24
Download 24 pages 62.44 Kb
Page 12
Image 12
Canadian Requirements

BFC36 Balance Flue Heat-Circulating Fireplace

Firestop spacers are not available for, nor are they required on vertical walls.

DO NOT put any sealant around the area where the outer pipe slides through the firestop spacer. If you seal this area, it may cause a fire hazard.

Canadian Requirements

for Insulation Shield

In Canada, an attic insulation shield is required to pre- vent attic insulation from contacting the chimney sec- tion. Framing dimensions for the chimney hole should measure 17¹⁄” x 17¹⁄” (445 x 445mm). An attic shield MUST be installed on top of attic joists (above the floor

Additional Ceilings

If you encounter additional ceilings, repeat same steps required for first ceiling installation. See firestop illus-

tration in Page 11, Figure 16.

Penetrating the Roof

Run pipe to roofline. Since chimney system must be vented to the out-of-doors, you must use an approved CFM Corporation termination.

If a chase is used, refer to the installation manual pro- vided with the termination cap.

Locate Chimney Centerpoint On Roof

level). (Fig. 17)

Attic Insula- tion Shield

Additional Ceilings Ceiling

Nails

(4 required)

Attic Joist

Base Flanges

FP263

Use same procedure detailed in locating center point of the flue system.

Drive a nail up through roof at the center point. This will

determine center point on outside of the roof.

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney termi- nation installed. Refer to installation instructions pro- vided with CFM Corporation chimney termination to find correct size of roof hole.

There must be a 1¹⁄” (38mm) air space between out- ermost portion of chimney sections and any adjacent combustible surfaces. (Combustible surfaces include burnable materials such as: ceiling members, joists, flooring, combustible insulation and roof structures.)

Fig. 17 Attic shield installation (Canadian requirement).

Continue Installing Pipe to Complete Run

Continue attaching pipe sections to complete system to next level always being careful that the pipe is firmly snap-locked in place before proceeding to next pipe

section.

Chimney Supports

If chimney supports are required, they are installed the same as elbows. Nail chimney support straps to ad- jacent structural framing, as shown on Page 8, Figure

9.Bend straps as necessary and make sure they are secure so they will support the weight of the chimney. A chimney support is 2¹⁄" (64mm) long when installed. Consider this dimension when determining how many straight chimney sections are needed.

NOTE: Chimney supports are generally used in long

runs in a chase installation.

WARNING: Do not pack required air spaces with insulation or other materials.

Mark an outline of the roof hole around the center of the point nail. NOTE: Hole dimensions given in the chim- ney top installation instructions are horizontal dimen- sions; therefore, the hole size must be marked on the roof accordingly.

Cover the opening of the installed chimney so debris cannot get into the system.

Cut and frame the hole. It is good practice to use fram- ing lumber that is the same size as the rafters. Install the frame securely because the chimney top and flash- ing anchored to the frame must be able to withstand heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your termination according to the Ten Foot Rule, continue to install pipe to the predetermined height.

Check the chimney top installation instructions for details on how high above the roof top the chimney sec- tions (all pipes) should extend.

12

7412647

Page 12
Image 12
Vermont Casting 647 BFC Canadian Requirements for Insulation Shield, Additional Ceilings, Penetrating the Roof, 7412647