Installation Guidelines
The fireplace must meet the minimum dimensions listed below. (Fig. 1) Do not install the logset if the fireplace does not meet these minimums.
|
| Minimum Fireplace Dimensions |
|
| |||
|
| A | B | C | D |
|
|
Logset | Gas | Front | Rear |
|
| Min. Input | Max. Input |
|
| Width | Width | Depth | Height | BTU/Hr. | BTU/Hr. |
18” - UC181N |
| 29” | 19” | 14” | 17” | 25,000 | 39,000 |
18” - UE181N |
| 29” | 19” | 14” | 17” | 25,000 | 39,000 |
24” - UC241N | Natural | 29” | 23” | 14” | 17” | 25,000 | 39,000 |
24” - UE241N |
| 29” | 23” | 14” | 17” | 25,000 | 39,000 |
18” - UC181L |
| 29” | 19” | 14” | 17” | 25,000 | 39,000 |
18” - UE181L |
| 29” | 19” | 14” | 17” | 25,000 | 39,000 |
24” - UC241L | Propane | 29” | 23” | 14” | 17” | 25,000 | 39,000 |
24” - UE241L |
| 29” | 23” | 14” | 17” | 25,000 | 39,000 |
B |
C |
A |
D
Fireplace Spacing Requirements
The illustration in Figure 2 shows spacing requirements for your room with a hood installed (not included).
Without a hood, you must maintain a minimum of 32” between the top opening of the firebox and the bottom of a mantel which protrudes out 12”. If you do not have at least 32” between the two, a hood must be installed.
With a hood installed, you must maintain a minimum of 24” between the top opening of the fireplace and the bottom of the mantel.
NOTE: The distance between any combustible material and the top opening of the fireplace must
Fig. 1 Minimum fireplace dimensions.
be a minimum of 18” above the opening.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Without Hood |
|
| With Hood | |||||||||||||||||||||||||||
|
|
| Ceiling |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 12" |
|
|
|
|
|
|
|
|
|
|
|
| 12" |
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 42" | Noncombustible |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Noncombustible |
|
|
|
|
|
|
| |||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Material |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Material |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 32" |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 24" |
| |||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Min. |
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Min. | ||||||||||||||
|
|
|
|
|
|
|
|
| 6" Min. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
| 18" |
|
|
|
|
|
|
|
|
| 8" |
|
|
|
|
|
|
|
| |||||||||||||||||||||
|
| Side Wall |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||||||||||||
|
|
|
|
|
| Min. |
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Min. |
|
|
|
| |||||||||||||||||||||||||||||||
NOTE: In all cases, the top of the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||
opening for the firebox must be a | Firebox |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||||||||||||
|
| Firebox | ||||||||||||||||||||||||||||||||||||||||||||||
minimum of 42” from the ceiling. The |
|
| ||||||||||||||||||||||||||||||||||||||||||||||
Opening |
|
| ||||||||||||||||||||||||||||||||||||||||||||||
side openings must be a minimum of |
|
| Opening | |||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Hood | ||||||||||||||||||||||||
6” from the closest side wall. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| FP1498 |
Fig. 2 Clearances to combustibles.