Vermont Casting UE241L, UC241L, UE181N Installation Guidelines, Fireplace Spacing Requirements

Models: UE241N UE181L UE181N UC241L UC181N UE241L UC181L UC241N

1 14
Download 14 pages 49.15 Kb
Page 5
Image 5
Installation Guidelines

Installation Guidelines

The fireplace must meet the minimum dimensions listed below. (Fig. 1) Do not install the logset if the fireplace does not meet these minimums.

 

 

Minimum Fireplace Dimensions

 

 

 

 

A

B

C

D

 

 

Logset

Gas

Front

Rear

 

 

Min. Input

Max. Input

 

 

Width

Width

Depth

Height

BTU/Hr.

BTU/Hr.

18” - UC181N

 

29”

19”

14”

17”

25,000

39,000

18” - UE181N

 

29”

19”

14”

17”

25,000

39,000

24” - UC241N

Natural

29”

23”

14”

17”

25,000

39,000

24” - UE241N

 

29”

23”

14”

17”

25,000

39,000

18” - UC181L

 

29”

19”

14”

17”

25,000

39,000

18” - UE181L

 

29”

19”

14”

17”

25,000

39,000

24” - UC241L

Propane

29”

23”

14”

17”

25,000

39,000

24” - UE241L

 

29”

23”

14”

17”

25,000

39,000

B

C

A

D

FD370-2

Fireplace Spacing Requirements

The illustration in Figure 2 shows spacing requirements for your room with a hood installed (not included).

Without a hood, you must maintain a minimum of 32” between the top opening of the firebox and the bottom of a mantel which protrudes out 12”. If you do not have at least 32” between the two, a hood must be installed.

With a hood installed, you must maintain a minimum of 24” between the top opening of the fireplace and the bottom of the mantel.

NOTE: The distance between any combustible material and the top opening of the fireplace must

Fig. 1 Minimum fireplace dimensions.

be a minimum of 18” above the opening.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Without Hood

 

 

With Hood

 

 

 

Ceiling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12"

 

 

 

 

 

 

 

 

 

 

 

 

12"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42"

Noncombustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Noncombustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min.

 

 

 

 

 

 

 

 

 

6" Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18"

 

 

 

 

 

 

 

 

 

8"

 

 

 

 

 

 

 

 

 

 

Side Wall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min.

 

 

 

 

NOTE: In all cases, the top of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

opening for the firebox must be a

Firebox

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Firebox

minimum of 42” from the ceiling. The

 

 

Opening

 

 

side openings must be a minimum of

 

 

Opening

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hood

6” from the closest side wall.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1498

Fig. 2 Clearances to combustibles.