2. Evaporator Unit
•The
•The
•Supply and return air flow from the evaporator unit shall be unobstructed for at least 1 foot.
•There is a gravity drain line so that it can not be installed above the evaporator unit. Otherwise a condensation pump must be used.
3. Refrigeration Piping and Charging
NOTES: ALWAYS USE THE SUPERHEAT AND SUBCOOLING, PRESSURE READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED CHARGES ARE FOR REFERENCE ONLY.
•The installation order starts from condensing unit (including the receiver), liquid line
•The subcooling at the condensing unit shall be around 10°F. The charge may be complete when there are no more bubbles forming in the sight glass.
•The evaporator superheat is set around
•Low side pressure: around 33 psig
•High side pressure: 130
The line sizes and refrigerant charges are listed as follows.
MODEL | REFRIGERATION | LIQUID | SUCTION | |
LINES | LINE | LINE | ||
| ||||
< 50 FT | 1/4" | 3/8” OD | ||
OD | ||||
|
|
| ||
< 50 FT | 1/4" | 3/8” OD | ||
OD | ||||
|
|
|
DRAIN
LINE
1/2” OD
3/8” OD
CHARGE
R134a/
15OZ R134a/
15OZ
4. Pressure, Superheat and Subcooling Readings
NOTES: THE SERVICE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY.
| Complaint |
| Possible Causes |
a. | High suction pressure and low head pressure | a. | Compressor may be bad |
b. | High suction pressure and low head pressure | b. | Expansion valve opened, too |
| Low superheat and low subcooling |
| much oil |
- 1 -