Vinotemp VINO4500DS, VINO6500DS, VINO8500DS manual Service Guide, Refrigeration Piping and Charge

Models: VINO4500DS VINO8500DS VINO6500DS

1 25
Download 25 pages 4.67 Kb
Page 14
Image 14
Service Guide

Service Guide

1. Refrigeration Piping and Charge

The subcooling at the condensing unit shall be around 10°F. The charge may be complete when there are no more bubbles forming in the sight glass.

The evaporator’s constant pressure expansion valve is set around 38- 40°F at factory. This pressure setting gives a dew point to maintain the humidity for storing wine.

The superheat at the evaporator unit shall be around 9-18°F under low and high load at 75°F ambient temperature.

Low side pressure: 33 psig

High side pressure: 130 -150 psig at 75 -90 °F ambient temperatures

MODEL

LIQUID

SUCTION

DUCT

DRAIN

CHARGE

LINE

LINE

LINE

 

 

 

VINO-4500DS

1/4" OD

1/2” OD

8

7/8” OD

R134a/

26 OZ

 

 

 

 

 

VINO-6500DS

1/4" OD

5/8” OD

10

7/8” OD

R134a/

32 OZ

 

 

 

 

 

VINO-8500DS

3/8" OD

5/8” OD

10

7/8” OD

R134a/

38 OZ

 

 

 

 

 

2. Pressure, Superheat and Subcooling Readings

NOTES: THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ PROPERLY.

 

Complaint

 

 

Possible Causes

 

a.

High suction pressure and low head pressure

a.

Compressor may be bad

 

b.

High suction pressure and low head pressure

b.

Expansion

valve opened, too

 

Low superheat and low subcooling

 

much oil

 

 

 

 

c.

High suction pressure and high head pressure

c.

Overcharge

 

 

 

 

 

Low superheat and high subcooling

d.

Non-condensable gas

 

d.

High to normal suction pressure and high head pressure

 

 

Low subcooling

e.

Air

restricted,

dirty

condenser,

e.

High suction pressure and high head pressure

 

Low subcooling

 

bad condenser fans

 

 

f.

High suction pressure and high head pressure

f.

High

room

temperature,

high

 

High superheat

 

evaporator load

 

 

 

g.

Low suction pressure and low head pressure

g.

Undercharge

 

 

 

 

High superheat and low subcooling

h.

Liquid

line

restricted

after

h.

Low suction pressure and low to normal head pressure

 

High superheat and high subcooling

 

receiver,

solenoid

valve

 

 

 

restricted

 

 

 

 

i.

Low suction pressure and low head pressure

i.

Suction line restricted

 

 

Low subcooling

j.

Air

restricted

at

evaporator,

j.

Low suction pressure and low head pressure

 

Low superheat and low subcooling

 

evaporator iced

 

 

 

- 13 -

Page 14
Image 14
Vinotemp VINO4500DS manual Service Guide, Refrigeration Piping and Charge, Pressure, Superheat and Subcooling Readings