Troubleshooting

WATLOW IND. WATROD Circulation Heater Installation & Maintenance Manual

I&M NUMBER: 316-42-5-1

Page: 5

Date: 6/11/2008

Rev: 2.00

________________________________________________________________________________________________________________________________________________________________________________________________________________________

plug. If leak persists, remove heating unit and add teflon tape or sealing compound to threads and re-install. Care should be taken to observe the orientation of the flange or plug to its original position.

Troubleshooting

PROBLEM

Cause / Correction

No power available to heater

Check disconnect switch to ensure it is in the "ON" position

 

and that fuses are not blown. Replace fuses if they are blown

Fuses blowing

Check heater electrical rating. Applied voltage may be wrong

 

Check fuse rating. Fuses should be at least 25% more than full

 

load amperage.

 

Disconnect heater power source. Check the heater resistance

 

to ground. This should be no less than 1 Megohm. Refer to

 

Megohm checking.

Not enough power

Check line voltage to ensure it is within specification

 

Check full line current if voltage is correct. If line current is lower,

 

the heater may be wired wrong or has open elements

Fluid not heating to desired

Not enough Kw

temperature

Too much heat loss

High limit tripping / alarm

Not enough fluid flow

 

Too much Kw

 

Line voltage higher than designed / allowable

Preventative Maintenance

CAUTION: HAZARD OF ELECTRIC SHOCK. TURN ALL POWER TO HEATER OFF, USE

! APPROPRIATE DISCONNECT LOCKOUTS AND ALLOW SYSTEM/HEATER TO COOL BEFORE

PERFORMING ANY MAINTENANCE

Check line connections to make sure they are tight, free of oxide build-up, and that no dust or dirt build-up is present. Retighten to 20 in-lbs as necessary.

Check enclosure (inside) for rust, dirt or dust. Remove rust if present, with steel wool (or equal) and thoroughly blow clean with dry, oil-free air.

If enclosure is moisture resistant, check condition of cover gasket. A replacement can be obtained from the factory.

Liquid immersed units should be removed from tank and checked periodically for scale build-up. Clean as required. Scale can cause high sheath temperature and result in inefficiency and shortened life. When the heater is removed or tightened, take care to orient the heater in the position it was originally oriented.

Replacement Parts

Reference the Circulation heater part number on the nameplate when ordering replacement parts. Recommended spare parts would be : an immersion heater, flange gasket, and thermostat (if supplied).