Chart 3
-
Operation Menu
Prompts and
Descriptions.
Dead Band: Enter the Dead Band between the heating and cooling functions
adjustable from
±
99°F/±
55°C.
The default is
0°.
Appears when Ot2
=
CL.
Alarm Low: Represents the low process alarm or low deviation alarm.
Displayed only when 0t2 parameter is AL.
Alarm High: Represents the high process alarm or high deviation
alarm. Displayed only when Ot2 parameter is AL.
Calibration Offset. The range is
±99°F/±55°C.
The default is
0°.
Calibration Offset adds or subtracts degrees from the input signal.
Auto-Tune. The range of this parameter is
0-3,
off
=
0, slow
=
1,
medium
=
2, and fast
=
3. A value other than 0 initiates the auto-tune.
Local-Remote: Selects a local or remote set point for the Series
980/985.
Local set point is adjustable directly from the
980/985,
while remote can only
be changed from an external device. The signal must be within
O-5V
or
4-
20mA process input. This parameter appears if the LOC parameter
=
0, 1 or 2,
and rSP
=
0-5 or 420.
If L-r
=
r,
the remote set point is displayed in place of the
internal set point.
Use this page as a master copy for your Series
980/985.
Operation Parameters.
Do not enter
any
values here: make
photocopies
instead.
1
Operation Parameters
Value
Range
Factory
Default
SP2
rL
to
rH
Same as primary set point.
Pbl
0
to
999°F/0
to
555°C
or
25°F/l3°C
(3 or 4 digit)
0
to
99.9°F/0
to
55.5°C
0=ON/OFF
control
with
3°F
or
1.7°C
switching differential.
0.3°F
or
0.17°C
for 0.10 units.
Pb2
Same as
Pb1
. Only appears if
0°F/0°C
(3
or
4 digit)
Ht/CL
or
CL/Ht
operation.
rE1
0.00 to 9.99
repeats/min.
0.00
repeats/min.
0.00
=
No Reset Action
rE2
Same as
rE1.
Only appears if
0.00
repeats/min.
Ht/CL
or
CL/Ht
operation.
Will not appear if Pb2
=
0.
rA1
0.00 to 9.99 min.
0.00 min.
0.00
=
No Rate Action
rA2
Same as
rA1.
Only appears
0.00 min.
if
Ht/CL
or
CL/Ht
operation.
Will not appear if Pb2
=
0.
AL0
-
Deviation
dE
-99°
to
(3 digit display)
-99°
-999°
to
(4 digit display)
-999°
Process
Pr
rL
to
AH1
rL
AHI
-
Deviation
dE
to
99°
(3 digit display)
99°
to
999°
(4 digit display)
999°
Process
Pr
AL0 to
rH
rH
Ctl
1 to 60 seconds
5 seconds
Ct2
1 to 60 seconds
5 seconds
Appears if
Ht/CL
or
CL/Ht
Will not appear if PB2 = 0
db
±99°F/±55°C.
0
Appears if
Ht/CL
or
CL/Ht
CAL
±99°F/±55°C
0
AUt
0-3
0
Appears if
Ot1
=
Ht.
L-r
L or
r.
Appears if
rSP
=
0-5
or 420.
28
WATLOW
Series
980/985
User’s Manual
Setup, Chapter 4