
Operating Instructions and Parts Manual
Troubleshooting Chart - CSECAP40, CSECAP50
Symptom | Possible Cause(s) | Corrective Action |
|
|
|
Pump will not start or run
1. Water level too low | 1. |
| water is within 1 inch of the top of the sensor. |
2. Blown fuse or tripped circuit | 2. If blown, replace with proper sized fuse or reset breaker |
breaker |
|
3. Low line voltage | 3. If voltage is under recommended minimum, check wiring |
| size from the main switch on property. If OK, contact |
| power company. |
4. Defective motor | 4. Return for service or replace motor |
5. Defective | 5. Replace |
6. Impeller (pump filled with | 6. If impeller will not turn, remove housing and remove |
debris) | debris |
7. Insufficient liquid level | 7. Make sure liquid level is at least 11" from the basin floor |
Pump starts and stops too often
1. Backflow of water from piping | 1. Install check valve |
2. Dirty | 2. Reposition pump, clean sensor face (Figure 3B). |
sensor |
|
3. Check valve not installed or | 3. Remove and examine check valve for proper installation |
leaking | and free operation |
4. Discharge head is less than | 4. Recheck all sizing calculations to determine proper pump |
manufacturer’s minimum | size |
Pump shuts off and turns on independently of switch (trips thermal overload protection)
1. Excessive water temperature | 1. Pump should not be used for water above 120° | |||
|
|
|
| Pump may start unexpectedly. |
|
|
|
| |
|
|
|
| |
|
|
|
| Disconnect power supply |
|
|
|
| |
|
|
|
| |
| before servicing | |||
2. Low line voltage | 2. If voltage is under recommended minimum, check wiring | |||
|
| size from the main switch on property. If OK, contact | ||
|
| power company |
| Pump operates noisily | 1. Worn bearings | 1. Return for service or replace |
| or vibrates excessively | 2. Debris in impeller cavity or | 2. Remove housing, clean impeller and/or replace broken |
|
| broken | impeller |
|
| 3. Piping attachments to building | 3. Replace portion of discharge pipe with flexible connector |
|
| structure too rigid or too loose |
|
|
|
|
|
| Pump will not shut off | 1. Defective | 1. Replace |
|
| 2. Restricted discharge (obstruction | 2. Remove pump and clean pump & piping |
|
| in piping) |
|
|
| 3. Excessive inflow or pump not | 3. Recheck all sizing calculation to determine proper pump |
|
| properly sized for application | size |
|
|
|
|
| Pump operates but | 1. Low line voltage | 1. If voltage is under recommended minimum, check wiring |
| delivers little or no |
| size from the main switch on property. If OK, contact |
| water |
| power company |
|
| 2. Debris caught in impeller or | 2. Remove, clean and check for tightness |
|
| discharge |
|
|
| 3. Worn or defective pump parts or | 3. Replace worn parts or entire pump. Clean parts if required |
|
| plugged impeller |
|
|
| 4. Pump running backwards | 4. Check rotation. (CCW from bottom) Return if CW |
|
| 5. Pump not properly sized for | 5. Recheck all sizing calculations to determine proper pump |
|
| application | size |
|
| 6. Check valve stuck closed or | 6. Remove and examine check valve for proper installation |
|
| installed backwards | and free operation |
|
| 7. Shut off valve closed | 7. Open valve |
www.waynepumps.com
6