Operating Instructions and Parts Manual
| Maintenance | Unplug the main pump and fill sump | 5. If pump operates normally, plug | ||
| (Continued) | 4. | |||
|
|
| with water until back up pump turns | PS/BC into wall outlet, turn on main | |
3. Inspect the terminals and clamps | on. Repeat process two times to be | pump. If pump fails to operate | |||
| for corrosion and tightness. Clean | sure pump is operating normally. | normally, see Troubleshooting guide | ||
| and tighten as required. |
| and correct problem. Repeat step 5. | ||
|
|
| |||
|
|
|
|
| |
| Troubleshooting Chart |
|
| ||
|
|
|
|
|
|
| Symptom | Possible Cause(s) | Corrective Action |
| |
|
|
|
|
|
|
|
| ESP45 | |
Pump Installation |
|
| |
Installation of this |
|
| |
unit may take |
|
| |
several hours. Before disabling your | Floor |
| |
main pump, have ready an appropriate | Joist |
| |
means of evacuating the sump. |
| Slope | |
1. Turn power to main pump off. | Ridgid | ||
Pipe | |||
2. Pump must be installed using 11/4” | PVC | Down | |
Pipe | |||
or 11/2” rigid PVC piping. |
|
| |
Pump Installation |
| Check Valve | |
The ESP45 can be installed as a back up |
| (See Step 6) |
Pump won’t run 1. Connections not secure
2.Low or defective battery
3.Float switch stuck
4.Defective or blown fuse
1.Check all connections
2.Check battery and replace if low or defective
3.Make sure nothing is interfering with operation of switch
4.Check internal fuse located on the PS/BC. Pull the charger from the wall outlet and remove. If the fuse is blown, replace it with an automotive type fuse of the same amp ratio.
system with a separate dedicated | PS/BC | |
discharge line (Method 1), or tied into |
| |
an existing sump pump line (Method 2). |
| |
Unplug the existing |
| |
AC pump. Failure to | Batteries | |
follow this warning could result in fatal | ||
| ||
electrical shock. | 11/4” or | |
1. Verify that the existing AC pump is | 11/2” | |
PVC Pipe | ||
in good working order. If the AC | ||
|
Motor hums but | 1. Defective battery | 1. Check battery and replace if low or defective |
pump won’t run | 2. Impeller is locked | 2. Unplug pump, volute, and check to see if impeller is free to turn. |
|
| If impeller is locked, remove the obstruction. Reassemble pump |
|
| and reconnect |
|
|
|
pump is questionable, it is typically |
|
| |
recommended that the unit be |
|
| |
replaced with a 1/3 or 1/2 HP pump. |
|
| |
2. Remove any silt or accumulated | Battery |
| |
debris from the sump pit and | Box |
| |
surrounding area. | ESP45 | Existing Pump | |
Pump | |||
|
|
Pump runs but pumps very little or no water
1.Check valve missing or improperly installed
2.Obstruction in discharge pipe or pump inlet
3.Discharge pipe length and/or height exceeds capacity of pump
4.Low or defective battery
1.Check to make sure check valves installed between primary pump discharge and Backup Sump Pump are functioning properly
2.Check for obstruction and clear if necessary
3.If discharge is too high, a separate line may be required with a lower discharge height
4.Check battery and replace if low or defective
Method 1 (Preferred) | Figure 2 - Method 1 |
| |
1. Locate the ESP45 on a solid, level |
|
| |
surface in the sump pit. Do not | 5. Place the pump with the 4’ section of | sloped downward so that water will | |
place the pump on a loose or sandy | PVC pipe on a solid, level surface in | not freeze in the pipe. | |
surface. Small stones or sand may | the sump pit on an elevated surface. | When installing the separate discharge | |
damage the pump resulting in |
| ||
6. Attach a rubber check valve (sold | pipe, drill through the outside wall with | ||
potential pump failure. | |||
separately) to the top of the | appropriate drilling equipment. Seal the | ||
2. This pump has a 11/2” NPT discharge. | |||
discharge pipe. This will allow the | hole to prevent water from entering. | ||
If a 11/4” discharge pipe is desired, |
| ||
pump or check valve to be removed | Method 2 | ||
an adapter (not included) will be | |||
|
|
Pump cycles too | 1. Check valve problem | 1. Check to make sure check valves installed between primary |
frequently |
| pump discharge and Backup Sump Pump are functioning |
|
| properly |
|
|
|
No yellow light | 1. Battery connection problem | 1. Verify battery connection is correct |
|
|
|
Red light is on | 1. Blown pump fuse | 1. Check fuse and replace with a fuse of same rating and size |
with alarm | 2. Low battery voltage | 2. Check battery voltage. PS/BC will not charge batteries with a |
|
| combined voltage of 21.6 VDC or less |
www.waynepumps.com
| necessary. Smaller diameter piping | easily for servicing. | If a separate, dedicated discharge is | |||||||
|
| |||||||||
| 7. Check valve is required for effective | not possible as in Method 1, the ESP45 | ||||||||
| will reduce pump flow, rate and | |||||||||
| operation of system. | pump can be tied in to the AC- | ||||||||
| performance. |
|
| |||||||
|
|
|
| operated pump’s discharge pipe by | ||||||
|
|
| 1 | 1 | /2" | NOTE: Check valves can be placed | ||||
|
|
|
| |||||||
3. Cut a 4’ section of 1 /4" or 1 |
| directly in the pump discharge if | installing a “Y” connector. Two check | |||||||
| diameter rigid PVC pipe. Cement | |||||||||
| valves will be required. | |||||||||
| desired. However, for ease of | |||||||||
1 | 1 | /4" pipe to a threaded fitting. | ||||||||
| ||||||||||
| disassembly, it is recommended that | 1. Locate the ESP45 on a solid, level | ||||||||
| Cement 11/4" pipe into pipe |
|
| |||||||
| coupling. Attach 11/4" pipe section | check valves be placed above the sump | surface in the sump pit. Do not | |||||||
| to the ESP45 discharge adapter. | as shown in Figure 2. | place the pump on a loose or sandy | |||||||
|
| surface. Small stones or sand may | ||||||||
4. Screw on to pump discharge. | The remainder of the discharge pipe | |||||||||
damage the pump resulting in | ||||||||||
|
|
|
|
|
|
|
| installation will vary depending on | ||
|
|
|
|
| Be careful not to | potential pump failure. | ||||
|
|
|
|
| individual circumstances. Using sound | |||||
|
|
|
|
| strip or cross thread |
| ||||
|
|
|
|
| plumbing practices, route the | 2. This pump has a 11/2” NPT discharge. | ||||
plastic fittings or check valves. Flex hose | ||||||||||
is not recommended. Rigid PVC or metal | discharge pipe to an exterior wall by | If a 11/4” discharge pipe is desired, | ||||||||
pipe is required for a permanent | the shortest path. Keep turns to a | an adapter (not included) will be | ||||||||
installation. |
|
| minimum because they reduce flow | necessary. Smaller diameter piping | ||||||
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| output of the pump. The pipe that | will reduce pump flow, rate and | |
|
|
|
|
|
|
|
| exits the building structure should be | performance. | |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| www.waynepumps.com |
6 | 3 |