GAS SUPPLY

GAS LINE PIPING

Refer to the piping chart at the bottom of previous page.

The corrugated gas line from the manifold is 58 inches long. Do not extend the gas line.

We have provided the means to make an SAE 45° flare connection. Do not use pipe sealant on this connection.

If the length of line required does not exceed 50 feet, use a 5/8” O.D. tube. One size larger should be used for lengths greater than 50 feet. Refer to piping chart.

Gas piping may be copper tubing, type K or L; polyethyl- ene plastic tube, with a minimum wall thickness of .062 inch; or standard weight (schedule 40) steel or wrought iron pipe.

Copper tubing must be tin-lined if the gas contains more than 0.3 grams of hydrogen sulfide per 100 cubic feet of gas.

Plastic tubing is suitable only for outdoor, underground use.

Gas piping in contact with earth, or any other material which may corrode the piping, must be protected against corrosion in an approved manner.

Underground piping must have a minimum of 18” cover.

TEST CONNECTIONS

All connections and joints must be thoroughly tested for leaks in accordance with local codes and all listed procedures

in the latest edition of the National Fuel Gas Code ANSI

Z223.1/NFPA 54.

DANGER

Do not use an open flame to check for gas leaks. Be sure there are no sparks or open flames in the area while you check for gas leaks. This will result in a fire or explosion which can cause serious bodily injury or death, and damage to property.

Typical 20 LP propane gas supply Instal- lation

We strongly recommend that you use the Summit® Built-In Tank Cabinet (#21280) for installations using a 20 lb LP cylin- der, mounted remotely in an “island” structure.

The Summit® Built-In Tank Cabinet is a CSA listed acces- sory for installing a remote mounted 20 lb LP cylinder, in an “island” structure. Summit® Built-In Tank Cabinet has a hose and regulator assembly and gas connections, for connecting a remote mounted LP cylinder to the Summit® Built-In gas grill. The hose and regulator is listed as a required part of the CSA listed Summit® Built-In gas grill.

The Summit® Built-In Tank Cabinet also meets the require- ments for venting, tank retention and separation of the LP cylinder from a heat source as outlined in the ANSI Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP enclosures.

The Summit® Built-In Tank Cabinet has its own installation guide.

If you do not use the Summit® Built-In Tank Cabinet, you need to hire a licensed contractor or licensed plumber and they need to follow the requirements described in the ANSI Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP enclosures.

The requirements described in the Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6. are as follows; A remote enclosure for an LP gas cylinder shall be ventilated by openings at both the upper and lower levels of the cylinder. This shall be accomplished by one of the following:

a). One side of the remote LP cylinder enclosure shall be completely open; or

b). If the remote LP cylinder enclosure is designed to have four sides, a top and a bottom, ventilation is required for the remote LP cylinder enclosure;

1). There should be at least two ventilation openings, (a hole or group of holes, for the purpose of ventila- tion) in the sidewalls of the enclosure. The openings should be located within 5 inches (127mm) of the top of the enclosure. The ventilation openings should be equally sized and spaced at a minimum of 90 degrees, and be unobstructed. The openings shall have a total free open area of not less than 20 square inches. (This relates to1 square inch of ventilation area, per pound of stored fuel capacity).

2). Ventilation openings (a hole or group of holes, for the purpose of ventilation) should be provided at floor level. The ventilation openings should have a total free area of not less than 10 square inches. (This relates to square of ventilation area, per pound of stored fuel capacity). There should be at least two ventilation openings if the ventilation openings at floor level are in the sidewall. The ventilation openings should be within 5 inches (127mm) of the floor. The ventilation openings should be of equal size and be spaced at a minimum of 90 degrees, and should be unobstructed.

3). The minimum size of the ventilation hole (s) should not be less than inch.

4). The ventilation openings in the sidewalls should not allow venting into the empty or “hollow” area of the “island”. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings in the sidewalls of the enclosure should only communicate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure.

c). If the remote LP cylinder enclosure has four sides, a top and a bottom, and is intended for installation in a built-in “island” enclosure;

4

Page 4
Image 4
Weber GOLD D, SILVER D, SILVER A dimensions GAS Line Piping, Danger, Test Connections