GOLD GV Ser. 3 — User’s information manual

User maintenance procedures (cont.)

Oil blower motor

Figure 2 Blower motor

6 MONTHS

1.Remove the jacket top panel to access the blower motor.

2.Use only S.A.E. 20 motor oil. DO NOT use household universal oils.

Use only S.A.E. 20 motor oil to lubricate the blower motor. Do not use common universal household oils.

3.See Figure 2.

4.Place a few drops of oil in each of the two oiler cups on the side of the blower motor.

Oil Oil blower motor cup

Oil cup Figure 2 Blower motor

85037

Operate boiler relief valve

1.Before proceeding, verify that the relief valve outlet has been piped to a safe place of discharge, avoiding any possibility of scalding from hot water.

To avoid water damage or scalding due to valve operation, a metal discharge line must be connected to relief valve outlet and run to a safe place of disposal. This discharge line must be installed by a qualifed heating installer or service technician in accordance with the instructions in the Boiler manual. The discharge line must be terminated so as to eliminate possibility of severe burns should the valve discharge.

2.Read the boiler pressure/temperature gauge to make sure the system is pressurized.

3.Lift the relief valve top lever slightly, allowing water to relieve through the valve and discharge piping.

4.If water flows freely, release the lever and allow the valve to seat. Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain. If the valve weeps, lift the seat again to attempt to clean the valve seat. If the valve continues to weep afterwards, contact your qualified service technician to inspect the valve and system.

5.If water does not flow from the valve when you lift the lever completely, the valve or discharge line may be blocked. Immediately shutdown the boiler, following the instructions on the inside jacket top Lighting Instructions. Call your qualified service technician to inspect the boiler and system.

END

OF SEASON

Part number 550-141-812/0699

Follow boiler shutdown procedure

1.Follow “TO TURN OFF GAS TO APPLIANCE” on the Lighting instructions on the inside of the jacket top panel. You will also find these instructions on pages 12 and 13 of this manual. Use the Lighting instruction for the gas valve model installed on the boiler.

2.Do not drain system unless exposure to freezing temperatures will occur.

3.Do not drain the system if it is filled with an antifreeze solution.

4.Do not shut down boilers used for domestic water heating. They must operate year-round.