PER Series 3
Pre-installation
General instructions
The
Low flow rates through the boiler at elevated temperatures should be avoided. The structure to be heated should be insulated in the conventional manner used in your area for electrically heated buildings. Boiler must be installed in accordance with these instructions so as not to void our warranty.
Open the boiler crate and check the contents. In the event of shortage or damage, notify the transportation company immediately.
Locating the boiler
The compact construction of the
Allow sufficient clearance above and below the boiler cabinet to permit installation of supply and return piping. A minimum of 6 inches is required at the top of the boiler for installation and accessories. A clearance of 10 inches is required on the right hand side for removal of the elements.
Expansion tank sizing
Undersized expansion tanks cause system water to be lost from relief valve and makeup water added through fill valve. Eventual section failure can result.
If a
Table 1 | Expansion tank sizing (Tank sizing based on 200 °F | ||
| average system temperature.) |
| |
|
|
|
|
Boiler | Standard |
| Additional |
model | (for series loop or |
| (for |
number | with convector baseboard) |
| |
No. 109 |
| No. 15 | |
|
|
|
|
No. 109 |
| No. 15 | |
No. 109 |
| No. 15 | |
|
|
| |
Note: Gravity systems converted to a forced hot water system usually require | |||
additional compression tank capacity. |
| ||
|
|
|
|
Mounting the boiler
Normally, the boiler will be installed against a frame or masonry wall. If the wall surface is rough or uneven, it may be necessary to mount plywood on the wall, then mount the boiler on the plywood. Refer to “Dimensions”on page 12 and “Ratings” on page 13, and note the boiler weight. Be sure that the wall structure will support the boiler and its piping.
The 9/16" top mounting holes and 5/16" lower mounting holes are on
1.Locate the top mounting holes so that the boiler will be level. Install the screws so that the heads protrude ¾" from the wall.
2.Raise the boiler to mounting position by placing a board across the bottom of the boiler or by grasping the lower left and right inside corners. Do not attempt to lift the boiler by grasping the bottom jacket cross tie.
3.Place the top brackets over the lag screws and then install screws through the lower mounting holes. The top screws can now be tightened.
Hydrostatic pressure test
Pressure test boiler before attaching piping or electrical supply.
1.Install air vent in tapping on top of boiler.
2.Plug remaining tappings, including relief valve opening.
3.Connect water supply. Fill boiler and purge all air. For more than 10 minutes,
Do not leave boiler unattended. Cold water fill could expand and cause excess pressure, resulting in severe personal injury, death or substantial property damage.
4.Check for maintained gauge pressure. Visually check for leaks if gauge pressure drops.
5.Drain boiler and repair leaks if found.
Leaks must be repaired at once. Failure to do so can damage boiler, resulting in substantial property damage.
6.Retest boiler after repairing leaks.
7.Remove testing plugs and air vent.
Do not use
Part number | 3 |