PER Series 3
Checkout procedure
After filling and purging, start the boiler as follows:
❏Turn the thermostat to its lowest setting so that there is no call for heat.
❏Set the limit control as recommended in the Installation Instructions.
❏Turn on the main electric switch to the boiler.
❏Set the thermostat above actual room temperature. Check for proper sequencing of elements. Heat the entire system to about 200°F so that dissolved air and gases in the system water will be emitted and vented.
❏Check limit control operation by lowering the control settings as described in the “Troubleshooting” section on page 7.
❏Restore the limit control settings to their recommended values and set the thermostat to the desired room temperature.
❏Fill in “Installation and service certificate” below.
❏If the boiler operates incorrectly or fails to start, refer to “Troubleshooting” on page 7.
Installation and service certificate
Boiler model __________________
Measured Btuh input ____________
Series __________ | CP number ___________ | Date installed _______________ |
❏Installation instructions have been followed.
❏Checkout sequence has been performed.
❏Above information is certified to be correct.
❏Information received and left with owner/maintenance person.
Installer ________________________ | ________________________________ | ______________________________ |
(company) | (address) | (phone) |
_____________________________________
(installer’s signature)
Part number | 9 |