Figure 10 Typical piping for multiple Ultra boilers,
1Flow/check valve (each boiler)
2Isolation valves (when used)
3Caps
4
5
6Primary circulator
7Expansion tank (diaphragm type)
8System air eliminator
9System automatic air vent
13Cold water supply
17Boiler circulator (each boiler)
18System supply
19System return
20Boiler relief valve and discharge piping, installed per Ultra Boiler Manual
21
22Boiler water inlet
23Boiler water outlet
24DHW
Suggested DHW
0 – 7 gpm | 1 inch | |
7 – 16 gpm | 1¼ inch | |
16 | – 24 gpm | 1½ inch |
24 | – 45 gpm | 2 inch |
45 | – 75 gpm | 2½ inch |
75 | 3 inch | |
140 – 290 gpm | 4 inch |
25DHW
26DHW
27Flow/check valves (to prevent induced or gravity flow in heating system or DHW piping)
28Check valve to prevent heat migration in heating system
29See water heater manual for DHW piping — The DHW piping must also be manifolded together since the
This piping is suggested only. The layout above should be controlled with a boiler sequencing panel that provides DHW operation as well. Wire the heating system circulator to operate only on call for heat. Alternatively, use the boiler sequencing panel to provide domestic priority by disabling the heating system circulator any time there is a DHW call for heat. The boiler circulators, item 17, must operate on any call for heat, whether heating system or DHW. Offset the DHW
Part number | 11 |