Placement and mounting information
REVIEW & COMMENT ONLY
CONFIDENTIAL
Placement, general
1.Locate multiple boilers in boiler room according to:
•Figure 3
•Figure 4
For wall mounting, see below.
2.Provide indicated clearances around boilers for access and servicing. If recommended di- mensions are not possible, re- fer to Ultra Boiler Manual for minimum clearances. Also fol- low local codes.
3.Construct boiler foundation if boiler room floor is uneven or if there is a danger of flooding. Size foundation to allow for clearance and spacing dimen- sions shown in either Figure 3 or Figure 4.
4.Chalkline boiler locations on foundation or boiler room floor.
5.Uncrate, assemble and mount boilers according to Ultra Boiler Manual.
6.Provide clearance for installa- tion of venting, air piping, gas piping, expansion tank, primary circulator and other accessories.
Wall mounting
1.Ultra boilers may be wall mounted, following the instruc- tions in the Ultra Boiler Manual and the Wall Mounting Supple- ment.
2.When wall mounting boilers, provide approximately 6 inches between boilers for easy re- moval of boiler jacket door. See Figure 5.
3.Follow all applicable codes re- garding piping, electrical con- nections and clearances.
4.When wall mounting boilers, verify the wall construction is suitable for the structural load.
Figure 3
Figure 4
Figure 5 Wall mounting multiple