GOLD
7c Start-up — if boiler doesn’t start . . .
Check for:
1.Loose connections, blown fuse or service switch off?
2.High limit switch set below boiler water tempera- ture?
3.Thermostat set below room temperature?
4.Gas not turned on at meter or boiler?
5.Incoming gas pressure less than:
5” w.c. for natural gas? 11” w.c. for propane gas?
6.If none of the above corrects the problem, refer to Troubleshooting, section 11 of this manual.
36 | Part Number |
|