Weil-McLain CGI-4E manual 3f Venting - direct exhaust - installation

Models: CGI-4E

1 68
Download 68 pages 59.15 Kb
Page 18
Image 18
3f Venting — direct exhaust — installation

GOLD CGi-4E Gas-Fired Water Boiler — Boiler Manual

3f Venting — direct exhaust — installation

1.Do not mix types or manufacturers of vent materi- als.

2.Clean all joints before sealing. See vent manufac- turer’s instructions for cleaning and sealing joints.

Use their specified sealant. Do not use screws.

3.Install vent pipe with seams on top of vent horizon- tal runs. Follow requirements in Section 3e for vent termination.

4.Maintain minimum 2” clearance from combustible materials to vent pipe.

5.Vertical venting — See Figure 13. Follow vent manufacturer’s instructions for venting through roof.

Vent pipe must extend through roof flashing, jacket or thimble.

Vent may pass through floor, inside wall or concealed space when installed according to vent manufacturer’s instructions.

Sidewall venting — See Figures 14 and 15.

Vent must terminate at least one foot above anticipated snow line. Vent must be termi- nated only with:

Tee or elbow with integral screen. (Tee may be mounted either vertically or horizontally.)

Elbow and termination coupling with screen (not available for StaR-34).

6.Do not seal vent pipe (slip connector for Saf-T Vent) to inside or outside plate.

7.If passing through noncombustible wall, provide hole diameter large enough to insert the vent pipe

(slip connector for Saf-T Vent).

8.Install horizontal drain tee as close as possible to boiler, in first horizontal run. See Figures 13 and 14.

9.Do not exceed the maximum vent system length given in Table 4, page 15.

Condensate drain line — use only silicone tubing rated for at least 400°F for the first 18” of condensate drain line, then other non-metallic tubing may be used. Us- ing any other material could cause flue gas leakage, potentially resulting in severe personal injury, death or substantial property damage.

On some installations, the condensate drain fitting may be omitted, provided:

Vent manufacturer shows this option in their instruc- tions.

Vent is sloped toward termination as shown in dotted lines in Figure 14.

The vent is installed per Weil-McLain and vent manufacturer’s instructions.

Condensate drippage from such vents may accumu- late on the ground below. Consider traffic in the area to avoid hazard due to ice accumulation.

Figure 13  Direct exhaust vertical venting

Figure 14  Direct exhaust sidewall venting

18

Part Number 550-110-711/1108

 

Page 18
Image 18
Weil-McLain CGI-4E manual 3f Venting - direct exhaust - installation, GOLD CGi-4E Gas-FiredWater Boiler - Boiler Manual