Western Telematic TAN-1005 manual SURGE SUPPRESSION FOR ZONE 0 LOCATIONS, Introduction

Models: TAN-1005

1 8
Download 8 pages 865 b
Page 3
Image 3
SURGE SUPPRESSION FOR ZONE 0 LOCATIONS

SURGE SUPPRESSION FOR ZONE 0 LOCATIONS

1 INTRODUCTION

For many years there has been general recognition that there is a significant problem from lightning strikes on installations such as stor- age tanks. The codes of practice for instrumentation in hazardous ar- eas for Germany and Holland both contain recommendations for spe- cific installation practice. In the United Kingdom the code of practice contains no detailed requirements and the problem has always been approached on an individual installation basis. Perhaps the clearest references are in the draft revision of the IEC code which contains two specific references to lightning problems. These, together with the rel- evant clause on potential equalisation, are quoted in full as an appen- dix (clauses 6.3, 6.5 and 12.3).

Although this code of practice has not yet been finally voted on and published it is likely to form the basis of accepted practice in signifi- cant parts of the world and forms a convenient reference document.

When a plant is struck by lightning then the point of impact would inevitably ignite a gas and air mixture that was present. Ignition at points other than the point of impact are dependent on the efficiency of bonding which must be adequate to prevent side flashes and hence bonding should have a low impedance as well as a low resistance. The majority of petrochemical installations are adequately bonded and sufficiently robust to prevent excessive lightning damage although some side flashes usually occur following a significant adjacent strike. Co- rona discharge from structures does occur in some atmospheric condi- tions and multiple streamers rising from structures to meet the usual lightning downward leader (which selects one of them) are a well es- tablished phenomenon. It is possible that if either a lightning flash, an upward corona streamer, or a side flash pass through a flammable mixture of gas then ignition will occur. In general, conventional bond- ing of a plant is considered adequate and the implications of possible lightning impact points are not considered a significant problem ex- cept in the case of vents which frequently discharge. Where lightning can damage the electrical insulation of power circuits there is a tran- sient potential hazard caused by the follow through of the power cir- cuit. This should however be rapidly removed by the electrical protec- tion ie. fuses, out of balance circuit breakers etc. which is a fundamen-

tal requirement of all the methods of protection used for power equip- ment. It is not usual for lightning induced current to directly cause enough heating to create a hazard by temperature ignition, since the current pulses are too short to create a sustained high temperature. However, vapourisation of flimsy conductors such as printed circuit tracks is not unusual. Overheating may occur if there is a power follow through of a fault initiated by the lightning induced voltage. It can be argued that if intrinsically safe apparatus is likely to be subjected to lightning dam- age then it is necessary to protect it since, following the lightning dam- age, its intrinsic safety may be impaired. There is no requirement in the apparatus standard to consider the effect of excessive surges, which are difficult to predict and could lead to damage. The problem should not be exaggerated, since lightning damage usually results in failure to a safe condition and also to operational failure and hence should be noticed and corrected. Possibly the need to repair or remove non- functional electrical equipment needs to be given further emphasis in the code of practice.

It is accepted that transient hazards during infrequent electrical faults can occur in Zones 1 and 2 providing that they are removed as quickly as is practical. The argument being that the coincidence of the poten- tially hazardous electrical fault and a flammable mixture of gas is suf- ficiently improbable to be acceptable. In the particular case of light- ning a similar analysis suggests that transient hazards caused by points of lightning impact and the occasional failure to bond adequately are possibly acceptable in Zone 1 and 2 but not acceptable in Zone 0. Fortunately the majority of Zone 0 locations are contained within proc- ess vessels which form an adequate Faraday cage which effectively prevents significant potential differences within the Zone 0 and hence the problem is generally controllable. Where problems are known to exist then special precautions are taken, for example the bond be- tween the floating roof of a storage tank and the tank itself is designed with considerable care, and subjected to frequent inspections. A prob- lem is introduced when the Faraday cage of the Zone 0 is broken by the introduction of equipment for measurement purposes.

Figure 1 shows an average contents temperature gauge being used in a storage tank and this illustrates the problem. The potential equalising network is shown diagramatically as a substantial structure intercon- nected electrically, in practice it is the plant structure bonded together. The transmitter protruding from the tank top is intended to illustrate the concept. In practice in a high lightning activity area it would be unwise to have the equipment protruding from the tank in this way since it would possibly invite a direct strike and could be the natural source of corona discharge. It should be provided with some mechanical protec-

100kA

L1

 

L2

 

10μS

 

 

30KV

 

 

 

30kV

 

 

Computer 0V

 

Potential equalising

Power 0V

 

 

 

network

 

10m

 

 

0.1μH/m

 

 

(10kV)

 

0.1μH/m

 

 

 

 

10kA

 

 

500m

 

 

(50kV)

 

 

Figure 1 Installation without surge protection

 

 

1

Page 3
Image 3
Western Telematic TAN-1005 manual SURGE SUPPRESSION FOR ZONE 0 LOCATIONS, Introduction