Step 8: Installing the Trip Finger

Step 9: Installing the Reset Arm Assembly

A.Note the position of the original Trip Finger and associated “gap” between the Trip Finger and manual Trip Shaft. Remove the original Trip Finger and scrap the mounting hardware.

B.Mount the new Trip Finger on the top of the Cross Bar (with the curve upward and the notch to the right) as shown, and the original Trip

Finger back on the bottom of the Cross Bar. Secure using the (2) .190-32 × 1.75" bolts,

(4)flat washers, (2) lock washers, and

(2)nuts supplied.

C.Verify that the original Trip Finger has been reinstalled in its initial position by checking the gap (noted in Step 8-A) between the original Trip Finger and manual Trip Shaft.

GAP

A.Remove the original Interlock Arm. Scrap the original bolts, washers, and nuts.

B.Mount the Reset Arm Assembly to the bottom of the Cross Bar and the original Interlock Arm

to the top of the Cross Bar in its original position, using the (2) .190-32 × 1.75" bolts, (4) flat washers, (2) lock washers, and (2) nuts supplied. The Reset Arm Assembly should be positioned so that the Reset Arm is hanging downward as shown.