MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

To set the parameter Sn-24 = 0

(VIN, 0 – 10 VDC)

Keypad Steps

Resulting Display

1 - Press the

PRGM

key

An – 01 -

DRIVE

Freq. Cmd. 1

 

 

 

 

 

 

 

 

 

2 - Press the

DSPL

key twice

 

 

Sn – 01 -

 

 

Inverter Capacity

 

 

 

 

 

3 - Press the

 

key until display shows

 

Sn – 24

 

 

 

 

 

 

 

External Input

Flashing

4 - Press the

5 - Press the

6 - Press the

7 - Press the

EDIT

ENTER key

key

EDIT

key to save.

ENTER

PRGM

DRIVE key to return to the main display.

Sn – 24 = 1

CMD. AIN

Sn – 24 = 0

CMD. VIN

Entry Accepted

Sn – 24 = 0

CMD. VIN

Flashing

2Seconds

Flashing

Step 9 – Select Feedback Engineering Units (P1-01) and Scaling (P1-02)

Initially the display will read output frequency in (Hz) as the factory default and is set by parameter (Cn-28=0).If (Cn-28)is changed to (=1), then the display will read out in (%). The setting of (Cn-28)is only valid if (P1-01=0),which is the factory default. Other engineering units may be selected by parameter setting (P1-01)as described on the following page.

In this step, the feedback engineering units that the system is controlling such as CPM in fan applications or PSI in the case of pumps can be selected by parameter (P1-01). (See Appendix A for additional selections). The maximum value that the engineering units will be in any given application is set by parameter (P1-02). These selections will now be displayed on the digital operator.

Example: A pump application that has a feeedback transducer with a maximum value of 200 PSI i.e 200 PSI = 20mA or 10 Vdc, can be set as shown next.

________________________________________________________________ 10

TECO – Westinghouse Motor Company

Page 10
Image 10
Westinghouse MA7200 Plus To set the parameter Sn-24 =, Select Feedback Engineering Units P1-01 and Scaling P1-02