MA7200 PLUS Inverter 1 to 2 HP PID Fan and Pump Quick Start Manual

__________________________________________________________________

________________________________________________________________

TECO – Westinghouse Motor Company 8
Step 7 – Setting Minimum Speed in Pump Applications

(NOTE: In the case of a fan application skip this step and go to Step 8)

In the case of pump applications it is normally required to limit the minimum speed that the
pump will operate regardless of the input speed command. The pump minimum speed is
usually specified either by the pump manufacturer or the application. Once this value has
been established, the minimum output frequency of the inverter and thus the minimum
motor (pump) speed can be set by parameter Cn-19. This parameter sets the minimum
inverter frequency output, and thus a minimum motor (pump) speed to a percentage of the
maximum output command frequency.
The following is an example of setting the minimum motor (pump) speed to 1800 RPM,
which is 50% of the maximum pump speed, 3600 RPM.
PRGM
DRIVE
DSPL Cn-01
key 3 times Input Voltage
1 - Press the
2 - Press the
4 - Press the key
key An – 01 -
Freq. Cmd. 1
Cn-19 = 000%
EDIT
ENTER key to save.
6 - Press the Entry Accepted 2 Seconds
PRGM
DRIVE
7 - Press the key to return to the main display.
Flashing
EDIT
ENTER
Flashing

To set parameter Cn-19 = 050%

(Minimum pump speed )
Keypad Steps Resulting Display
3 - Press the key until the display shows Cn-19
Freq Cmd Low Bound
Freq Cmd Low Bound
RESET key twice; then the key 5 times
5 - Press the Cn-19 = 050%
Flashing
Freq Cmd Low Bound
Cn-19 = 050%
Freq Cmd Low Bound